Coupled Multi-Physics Study on SF6 Decomposition Gas Diffusion and Sensor Placement Optimization in GIS Busbars.
Duohu Gong, Niyar Di, Yadi Xie, Shan Li, Ruyue Mai, Tong Li, Qian Shi
Electric Power Research Institute of State Grid Xinjiang Electric Power Co., Ltd., Urumqi 830011, China.
Key points
From the paper's conclusion- The findings reveal that fault source location significantly influences concentration response speed and spatial distribution patterns; SO2, HF, H2S, and SOF2 exhibit distinct diffusion characteristics due to their differing physical properties; and initial concentration primarily affects the non-uniformity during the early diffusion stage.
Abstract
Traditional fault diagnosis methods for gas-insulated switchgear (GIS) equipment primarily rely on offline detection and periodic maintenance, which suffer from limitations such as poor real-time performance and localization difficulties, thereby compromising the safe and stable operation of ultra-high-voltage power grids. To enhance the accurate identification and localization capabilities of defects within GIS equipment, this study first establishes a multi-physics coupled simulation model integrating temperature field, flow field, and concentration field to analyze gas diffusion characteristics under varying conditions of fault source locations, decomposition product types, and initial concentrations. Subsequently, a GIS busbar gas chamber experimental platform is constructed to validate the simulation model. Finally, a response time matrix, a peak concentration matrix, and a fault coverage index are developed, and a weighted comprehensive evaluation method is employed to optimize sensor placement schemes. The findings reveal that fault source location significantly influences concentration response speed and spatial distribution patterns; SO2, HF, H2S, and SOF2 exhibit distinct diffusion characteristics due to their differing physical properties; and initial concentration primarily affects the non-uniformity during the early diffusion stage. The simulation results demonstrate good agreement with experimental data, with a maximum root-mean-square error of 3.936 × 10-4. Monitoring point M4 achieves the highest comprehensive score, making it the preferred location for single-sensor deployment. These results provide a theoretical foundation and technical guidance for GIS online monitoring and fault diagnosis.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- A Study on a Digital Twin Method for Modelling the Diffusion Process of Fault Gases Inside High-Voltage Switchgear Combining Virtual and Physical Models.Sensors (Basel, Switzerland) · 2026
- A Virtual–Physical Sensing Method for Fault-Gas Source Localization in High-Voltage SwitchgearEnergies · 2026
- Review of Insulation Defect Detection Methods for a Gas-Insulated SwitchgearEnergies · 2026
- Design and Analysis of Functionally Graded Delta-Type Spacer in a Three-Phase Green Gas-Insulated Busduct Under Various AbnormalitiesDesigns · 2026
- SF6 Concentration Recognition Under Variable Humidity for GIS Leakage Monitoring Using Gramian Angular Summation Field and a Two-Stage CNNSensors · 2026
- Detecting Decomposition Gases from Gas-Insulated Switchgear with Cavity-Enhanced Polarization-Differential Raman SpectroscopyAnalytical Chemistry · 2026