Benchmarking of Multi-Modal Partial Discharge Sensors and a Cross-Modal Corroboration Framework for Noise Discrimination in Air-Insulated Medium-Voltage Metal-Clad Switchgear.
Tohid Shahsavarian, Ryan D Sparacino, Mavis Bekoe, Jason Cook, Vincent Tanguay
Applied Technology Services (ATS), Pacific Gas and Electric (PG&E), San Ramon, CA 94583, USA.
Key points
From the paper's conclusion- This study presents a laboratory benchmark performed on an actual 15 kV metal-clad switchgear assembly, incorporating representative PD source configurations and interferences encompassing electrical, acoustic, and electromagnetic noise.
Abstract
Reliable partial discharge (PD) assessment of air-insulated medium voltage (MV) metal-clad switchgear is challenged by the close proximity of adjacent units and the noise environment generated by control, relay, and mechanical or electromechanical equipment within the substation. Combined sensing approaches have been employed to identify primary PD sources and distinguish them from interference signals. Although individual sensing technologies have been extensively studied, no systematic framework has been established to corroborate readings across sensing modalities under controlled, reproducible noise conditions. This study presents a laboratory benchmark performed on an actual 15 kV metal-clad switchgear assembly, incorporating representative PD source configurations and interferences encompassing electrical, acoustic, and electromagnetic noise. Sensors spanning multiple detection classes were evaluated, including acoustic sensors (intrusive and remote airborne, and surface-contact types), high-frequency current transformers (HFCTs), transient earth voltage (TEV) sensors, and a wideband electromagnetic sensor, across both open-access and closed-panel configurations. Testing showed that electrical and electromagnetic noise primarily affects conducted-electrical and radiated-EM channels, while acoustic noise degrades acoustic sensors, leaving each channel type largely unaffected by the other's interference. This complementary behavior supports a two-path corroboration criterion that reduces false positives and false negatives and informs practical sensor selection for field deployment.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Partial Discharge Detection and Localization in Power Transformers Using an Integrated Fiber‐Optic Acoustic Monitoring FrameworkJournal of Sensors · 2026
- Optical fiber sensing and partial discharge fault diagnosis for power cable health monitoringMeasurement Science and Technology · 2025
- Study on Acoustic Emission Signals Generated by Partial Discharges Under DC StressSensors · 2026
- A VHF-Voltage Double Time Integral Method for Apparent-Charge Estimation of Partial Discharge in Gas-Insulated Switchgear.Sensors (Basel, Switzerland) · 2026
- Flexible UHF Antenna Sensor for Partial Discharge Detection of High-Voltage Cable JointsMeasurement Science and Technology · 2026
- Review of Insulation Defect Detection Methods for a Gas-Insulated SwitchgearEnergies · 2026