Flexible UHF Antenna Sensor for Partial Discharge Detection of High-Voltage Cable Joints
M. A. TAHER, Mohamadariff Othman, Hazlee Illias, Tarik Abdul Latef, S. M. Kayser Azam, Tengku Faiz Tengku Mohmed Noor Izam, A. K. M. Zakir Hossain, Mohd Fauzi Zanil,
Key points
From the paper's conclusion- The multi-layer, flexible substrate-based sensor is experimentally validated for PD detection on Cross-Linked Polyethylene (XLPE) cable joints.
Abstract
Partial discharge (PD) detection is essential for maintaining the reliability and operational safety of high-voltage (HV) power systems by identifying insulation degradation before catastrophic failure occurs. Conventional PD detection systems often depend on rigid antennas, which are difficult to install on HV cable joints and curved surfaces of HV equipment. To address this limitation, a flexible polyimide-based ultra-high-frequency (UHF) planar antenna sensor is presented in this work. The multi-layer, flexible substrate-based sensor is experimentally validated for PD detection on Cross-Linked Polyethylene (XLPE) cable joints. The antenna features a multi-stacked substrate-based coplanar waveguide (CPW) design. Under extreme bending conditions (35 mm bending radius), it can maintain 0.91-3 GHz UHF band coverage with an average gain of 2.44 dB. During PD detection tests, the proposed antenna sensor recorded significantly higher signal amplitudes compared to the conventional high-frequency current transformer (HFCT) method, demonstrating its suitability for field applications with reliable fault detection capability. The proposed sensor has a dimension of 146 mm × 100 mm and a total thickness of 0.675 mm only. Under extreme bending scenario, it can withstand mechanical deformation, keeping its performance satisfactory compared to other flexible PD sensors. In this work, the proposed flexible PD sensor is optimized, fabricated, measured and tested on XLPE cable joint for early detection of PD which offers a practical solution for on-site PD monitoring to ensure the predictive maintenance and safe operation of HV systems.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Research on Partial Discharge Signal Propagation Characteristics of UHV Core Reactor and Optimization of Measuring Points on Oil Tank WallIEEJ Transactions on Electrical and Electronic Engineering · 2026
- Optical fiber sensing and partial discharge fault diagnosis for power cable health monitoringMeasurement Science and Technology · 2025
- Benchmarking of Multi-Modal Partial Discharge Sensors and a Cross-Modal Corroboration Framework for Noise Discrimination in Air-Insulated Medium-Voltage Metal-Clad Switchgear.Sensors (Basel, Switzerland) · 2026
- Quasi-Distributed Partial Discharge Monitoring System with Remote Demodulation Based on DFB-FL/Interferometer Hybrid Sensing.Nanomaterials (Basel, Switzerland) · 2026
- Flexible Wireless Passive Resonance Ring Sensor for Nondestructive Crack Monitoring of Metal Structures.Micromachines · 2026
- Physics-Guided Dual-Domain Transformer for Reliable Partial Discharge Recognition of Power Cable Insulation under Heterogeneous Acquisition ConditionsEngineering Research Express · 2026