Determination of the Optimal DC/AC Ratio of a 10 MWe Licensed Commercial Photovoltaic Power Plant: A Financial Analysis for Efficient AC Capacity Utilization
Abdülkadir Sipahi, Serkan Sezen
Key points
From the paper's conclusion- In this study, the optimum DC/AC ratio was determined financially for a photovoltaic power plant (PVPP) in Niğde/Edikli with 15.237 MWp installed DC and 10 MWe licensed power.
Abstract
In grids with limited transformer and transmission–distribution capacity, the licensed power of solar plants is defined on the AC side, and capacity overshoot is not permitted. Since photovoltaic (PV) panels rarely reach standard test conditions, a DC/AC ratio above 1.0 with inverter power limitation can use licensed capacity more efficiently, though increasing ratios bring clipping losses. In this study, the optimum DC/AC ratio was determined financially for a photovoltaic power plant (PVPP) in Niğde/Edikli with 15.237 MWp installed DC and 10 MWe licensed power. Simulated with PVSOL at a 1 min time step and compared month by month with SCADA data, the model reproduces the annual energy delivered to the grid of 2021 to a relative deviation of −2.66% and the performance ratio to −1.93%; the comparison is reported as a long-term yield consistency check, since the simulation is driven by a climate dataset covering 2001–2020 while the measurement covers a single year. Unlike the generalized kWp-based cost approach in the literature, 25 scenarios (10–16 MWp; DC/AC 1.0–1.6) were examined using an item-based cost model separating costs affected and unaffected by installed power. Raising installed power from 10 to 16 MWp increased grid-delivered energy by ~41.9%, while clipping loss rose from less than 0.01% to 13.38%. At a real discount rate of 8% and over a 25-year assessment period, the discounted payback period (9.42 years), the internal rate of return (12.32%) and the levelized cost of energy (0.0823 USD/kWh) reach their best values jointly at 12.75–13.00 MWp (DC/AC 1.275–1.30). Because the three indicators vary only slightly between neighboring configurations, the result is reported as the economically viable range of 12.00–14.00 MWp (DC/AC 1.20–1.40), within which all three remain within 0.9% of their best values. The position of this range is conditional on the item-based cost-scaling rule: the constant-cost-per-kWp model places the ratio-based optimum at 10.50–11.00 MWp, and fixing half or all of the four site items places it at 13.50–14.00 and 14.50–15.25 MWp. The net present value at the same discount rate reaches its maximum of USD 4,429,253 at 14.25 MWp and therefore favors the upper part of that range.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Seasonal Performance Assessment and Optimisation of a Utility-Scale Single-Axis Tracking Bifacial Photovoltaic Inverter Block in the Al-Madinah Region, Saudi Arabia, Using Multiple Analytical ToolsEnergies · 2026
- AC Assessment of DC Power Flow Screening for Data Center Hosting Capacity and SitingarXiv · 2026
- Physical Modeling and Optimal Sizing of Photovoltaic Generation Systems for Estimating Firm Energy Under Colombia’s Reliability Charge (ENFICC)Clean Technologies · 2026
- Optimal siting and sizing of pumped-storage power plants in a multi-HVDC-infeed regional power grid via AC security feedbackFrontiers in Energy Research · 2026
- From Techno-Economic Optimization to Implementable Low-Carbon Residential PV Systems Using an Integrated Rooftop, Grid, and Decarbonization FrameworkEnergies · 2026
- Machine-Learning-Based Cost Efficiency Estimation of Photovoltaic Power Plants in ChinaSustainability · 2026