From the paper's conclusion- The results indicate that, when the total water flow rate is low, i.e., the water mist curtain is insufficient to block smoke, changing the nozzle arrangement has only a limited effect on downstream temperature, although the upward flow becomes stronger with more nozzles per row.
Abstract
Controlling fire-induced smoke in tunnels remains a critical issue in tunnel fire safety. This study investigates the use of a water mist curtain to contain fire-induced heat and smoke through small-scale experiments and Fire Dynamics Simulator (FDS) modeling. Reduced-scale tunnel tests first show that a properly arranged water mist curtain can limit the downstream spread of hot smoke under natural ventilation. Full-scale simulations are then used to examine the effects of the number of nozzles per row, row spacing, and total water flow rate for heat release rates (HRRs) from 1000 to 5000 kW. The results indicate that, when the total water flow rate is low, i.e., the water mist curtain is insufficient to block smoke, changing the nozzle arrangement has only a limited effect on downstream temperature, although the upward flow becomes stronger with more nozzles per row. Increasing the total water flow rate enhances the cooling effect and induces a reverse-flow region near the water mist curtain, making it more difficult for fire-induced smoke to pass through the water mist zone. Based on the theoretical analysis and simulation results, a dimensionless momentum ratio (the water-mist momentum to the smoke momentum), R=MwMs, is proposed to evaluate the smoke blocking effect of water mist curtains. A critical value of R = 24 is identified for the tested HRR, water mist curtain and tunnel geometry.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Study on Smoke Control Strategies for Tunnel Fires Under Near-Critical Velocity ConditionsFire · 2026
- Impact of Blockage Ratio on Smoke Control in High Heat Release Rate Tunnel Fires.ACS omega · 2026
- Fire Smoke Transport in Inclined Evacuation Passages of Deep-Buried Metro Stations: A Reduced-Scale Experimental StudyFire · 2026
- Characteristics of smoke propagation velocity and backlayering stratification in longitudinally ventilated herringbone-slope tunnelsPhysics of Fluids · 2026
- Analysis of Smoke-Spread Characteristics in Electric Vehicle Fires in a Two-Lane Tunnel with an Arched CeilingFire · 2026
- Vision-Guided Dual-Loop Control of a Truck-Mounted Electric Water Cannon for Autonomous Fire SuppressionApplied Sciences · 2026