Study on Smoke Control Strategies for Tunnel Fires Under Near-Critical Velocity Conditions
Xiaokun Zhao, Yafei Tian, Xiangzhong Zhang, Anyu Song, Wencai Wang, Donghui Yang
Key points
From the paper's conclusion- The results show that, without a water curtain, 15 m3/s is a representative suitable smoke extraction rate among the discrete cases; with 500 μm droplets and a flow rate of 40 L/min per nozzle, the 18 m3/s case exhibits comparatively favorable smoke control performance after the water curtain is introduced.
Abstract
High-temperature toxic smoke from tunnel fires poses a serious threat to safe evacuation, while direct experimental support is still lacking for the performance transition and parameter matching resulting from the combined action of centralized smoke extraction and a water curtain under near-critical longitudinal ventilation. To investigate their combined smoke control performance under near-critical longitudinal ventilation, this study combines FDS numerical simulations, 1:10 reduced-scale experiments, and dimensionless analysis to examine the effects of the smoke extraction rate and water curtain parameters on temperature and CO concentration in an 8 MW tunnel fire. The results show that, without a water curtain, 15 m3/s is a representative suitable smoke extraction rate among the discrete cases; with 500 μm droplets and a flow rate of 40 L/min per nozzle, the 18 m3/s case exhibits comparatively favorable smoke control performance after the water curtain is introduced. As the flow rate per nozzle increases from 30 to 60 L/min, the smoke extraction performance transition interval shifts from 17–18 to 20–21 m3/s, and a dimensionless interval-constrained relation is established: Πe = 3.90596Πw + 0.32834. This relation applies to the fixed geometry, fire, ventilation, and spray conditions in this study and is not for direct use in engineering design.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Smoke Blocking by Water Mist Curtains in Tunnel Fires: A Parametric Study and Momentum-Ratio CriterionFire · 2026
- Impact of Blockage Ratio on Smoke Control in High Heat Release Rate Tunnel Fires.ACS omega · 2026
- Analysis of Smoke-Spread Characteristics in Electric Vehicle Fires in a Two-Lane Tunnel with an Arched CeilingFire · 2026
- Smoke characteristics of conveyor-belt fires in U-shaped belt-conveyor roadways under different ventilation velocities.PloS one · 2026
- Numerical Assessment of Smoke Spread and Evacuation Safety for a Battery Electric Vehicle Fire in a Single-Lane Road TunnelFire · 2026
- Evacuation behaviour under smoke conditions in a real-scale road tunnel experiment in PolandScientific Reports · 2026