System-Level Optimization of Hybrid Diode–Thyristor Fault Current Limiters for Multi-Terminal HVDC Protection

Ali Raza, Iqra Sharif, Muhammad Ameer Hamza, Amin Akhtar, Ahmed Ali, Akhtar Rasool

Key points

From the paper's conclusion
  • The results demonstrate that the optimized FCL parameters effectively limit the DC fault current under the evaluated fault conditions and satisfy the specified protection constraints.

Abstract

Voltage source converter (VSC)-based high-voltage direct current (HVDC) systems face a critical challenge during DC-side faults and require rapid fault current limitation to ensure effective system protection. Conventional DC reactors are widely used for limiting fault currents. However, higher inductance levels can increase the energy-dissipation requirements and voltage stress of the DCCB metal-oxide varistor (MOV), which can impose additional requirements on the breaker. Therefore, appropriate FCL parameter selection is required to achieve effective fault current limitation while satisfying the protection constraints. To overcome these challenges, this paper proposes a hybrid diode–thyristor (D–T) fault current limiter (FCL) based on power electronic technology. In addition, the hybrid structure reduces the required number of thyristors and provides a potential equipment-cost advantage over existing DC fault current limiting solutions. Furthermore, an extended system-level parameter-design framework is developed for the D–T FCL by incorporating converter-side fault current infeed into the state-space fault current formulation and considering the coordinated effects of multiple FCL parameters in the MT-HVDC network. The state-space/RK-4 formulation is used as a computational model for repeated fault current evaluations during the parameter optimization process, while the optimized parameters are subsequently evaluated in PSCAD/EMTDC on a four-terminal VSC-HVDC network under different fault conditions and fault locations, demonstrating effective fault current suppression while satisfying the specified converter and DCCB protection constraints. The results demonstrate that the optimized FCL parameters effectively limit the DC fault current under the evaluated fault conditions and satisfy the specified protection constraints.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

System-Level Optimization of Hybrid Diode–Thyristor Fault Current Limiters for Multi-Terminal HVDC Protection — Science Skim