Energies

Physically Interpretable Series Arc Fault Detection via Hilbert Transform-Derived Half-Cycle Energy Ratios and LightGBM

Shoukang Luo, Zhe Li, Yubo Zhang, Jiahui Lin, Yang Li, Wenjing Sun, Chuanzhen Jia, Yaping Du

Key points

From the paper's conclusion
  • These results demonstrate a favorable balance among detection performance, physical interpretability, and deployment efficiency for resource-constrained arc-fault detection devices.

Abstract

Series arc faults in low-voltage AC distribution systems pose a significant fire hazard but are difficult to detect because the fault current may remain below the operating thresholds of conventional circuit breakers and residual current devices. This paper proposes a physics-guided and lightweight detection framework that combines Hilbert-domain transient analysis, Half-Cycle Instantaneous Energy Ratio (HIER) modeling, and an edge-constrained LightGBM classifier. A test platform compliant with GB/T 31143 was constructed to acquire high-sampling-rate current signals from eight representative resistive, inductive, and nonlinear household loads under normal and series-arcing conditions. By treating each AC half-cycle as the fundamental modeling unit, three complementary HIER descriptors were developed to quantify localized energy bursts, out-of-band spectral dispersion, and frequency–amplitude instability. These descriptors were combined with analytic-signal envelope, instantaneous-frequency, and Teager–Kaiser energy features and aggregated over a 100 ms sliding window to form a compact 13-dimensional feature vector. On the reference test set, the proposed model achieved an accuracy of 98.52%, an arc-fault recall of 99.26%, an F1-score of 98.47%, and a ROC-AUC of 99.85%. Ablation experiments confirmed that the HIER descriptors provide complementary discriminative information, while SHAP analysis showed that the classifier decisions are consistent with the transient-energy and non-stationary characteristics of arc discharge. The complete model occupied approximately 0.53 MB, and tree-prefix pruning reduced its size to 194.2 KB while maintaining an F1-score above 0.98. These results demonstrate a favorable balance among detection performance, physical interpretability, and deployment efficiency for resource-constrained arc-fault detection devices.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Physically Interpretable Series Arc Fault Detection via Hilbert Transform-Derived Half-Cycle Energy Ratios and LightGBM — Science Skim