Quiet-State-Anchored Simulation-to-Reality Adaptation for Arcing High-Impedance Fault Detection
Zengyao Tian, Shanwen Ke, He Song, Ronghui Xue
Key points
From the paper's conclusion- We therefore set the operating threshold as a score quantile of amplitude-silent unlabeled target windows and refine the model by two rounds of conservative self-training.
Abstract
High-impedance fault detectors are commonly trained in simulation, yet their transfer to physical arcing remains poorly quantified. Using a report-calibrated source generator and 983 physical vegetation-conduction tests from the Vegetation High-Impedance Fault (VeHIF) data set, we found that a compact one-dimensional convolutional neural network (1-D CNN) retained strong target ranking (area under the receiver operating characteristic curve (AUROC) 0.985), but its source-domain threshold reduced F1 to 0.628: decision calibration dominated the transfer gap. We therefore set the operating threshold as a score quantile of amplitude-silent unlabeled target windows and refine the model by two rounds of conservative self-training. Across ten seeds, the detector achieved F1 0.950±0.024 and AUROC 0.990±0.002, which was 32.2 F1 points above source-threshold transfer (paired Wilcoxon p=0.002); five further recording-wise splits reproduced the comparison. With a 3-of-5 persistence rule, 94.8% of fault tests raised an alarm (median decision-complete delay 0.6 s) and no background or non-ignition recording did; the pooled pre-fault window rate of 10.3% (11.8–16.2% on further splits) came from sub-threshold conduction in about 9% of tests. Surrogate tests showed that the detector responds to arc waveform shape but not current presence. On an independent 60 Hz covered-conductor campaign, a zero-shot check retained partial ranking (AUROC 0.89) but required re-anchoring to its quiet state. Quiet-state anchoring is thus a practical label-free calibration for channels dominated by the fault-loop current; superposed load current and arcing loads remain outside its scope.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Arc-Fault Detection Using Stage-Wise Alignment and Feature Fusion of Dual Learnable Time-Frequency Representations.Sensors (Basel, Switzerland) · 2026
- Physically Interpretable Series Arc Fault Detection via Hilbert Transform-Derived Half-Cycle Energy Ratios and LightGBMEnergies · 2026
- A Real-Time Series Arc Fault Detection Method for Residential Buildings Based on the Arc-FcaTCN and AIBCMeasurement Science and Technology · 2026
- A Hybrid Two-Stage Machine Learning Pipeline for Fault Detection and Classification in Power Transmission SystemsarXiv · 2026
- Hybrid CNN-decision tree framework for efficient transmission line fault detection and classification: an XAI-based approachScientific Reports · 2026
- Physics-Informed Machine Learning for UHVDC Transmission-Line Fault Identification: How Robust Is Near-Perfect Synthetic Accuracy to Simulation Fidelity?Energies · 2026