Strong-Tracking Observation of Generator Relative Rotor Angle for Transient Control of Cross-Voltage-Level Back-to-Back Converter Stations
Canran Yang, Hongli Zheng, Donglei Sun, Tong Liu, Yongzhi Zhou, Bin Yang, Zhenhua Yuan
Key points
From the paper's conclusion- Transient control of back-to-back (BTB) converter stations requires a generator relative-rotor-angle signal that remains responsive to post-fault swings while resisting measurement noise.
Abstract
Transient control of back-to-back (BTB) converter stations requires a generator relative-rotor-angle signal that remains responsive to post-fault swings while resisting measurement noise. Noisy rotor-angle measurements can trigger premature control actions, whereas excessive filtering can delay exit decisions. This study develops a power-corrected strong-tracking observer for generator relative rotor angle. Starting from a reduced-order relative-angle dynamic model, the observer introduces an AC-power recovery correction coefficient and an active-power measurement constraint to form a three-state observation model. A strong-tracking factor and a Huber-type innovation saturation mechanism are incorporated to retain fast post-fault tracking while suppressing strong-noise disturbances. Offline and closed-loop PSCAD simulations on a three-machine nine-bus system with a 500 MVA BTB station show that, under two-degree rotor-angle measurement noise, the proposed observer improves full-period estimation accuracy relative to a standard extended Kalman filter and a two-state strong-tracking EKF, while preserving low fault-window errors across fault durations. Closed-loop tests further show that the observer avoids premature emergency-power-control exit caused by noisy direct input and delayed exit caused by low-pass-filter lag. Under five-degree noise across ten tested random seeds, the observer reduces the observed counts of delayed exit and instability in the considered PSCAD cases, providing a real-time input for transient control of the tested BTB system.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- “High‐Accuracy Fault Detection and Compensation in Boost Converters: An Observer‐Based Approach With 3‐Sigma Threshold”International Transactions on Electrical Energy Systems · 2026
- Measurement Uncertainty-Bounded Transformer Differential Protection for Islanded Converter-Dominated Power SystemsApplied Sciences · 2026
- Output Voltage Control of a Half-Bridge LLC Resonant Converter Based on Nonsingular Fast Terminal Sliding Mode Active Disturbance Rejection ControlEngineering Research Express · 2026
- A Unified Control and Fault Diagnosis Framework for Single-Area Load Frequency Control: Addressing Sensor Bias Fault Insensitivity in Integral Control ApproachesElectronics · 2026
- Adaptive Damping Control for Stability Enhancement of Grid-Following Converters Based on q-Axis Voltage Magnitude FeedbackEnergies · 2026
- Dynamic State Estimation for a Back-to-Back VSC-HVDC Sending-End System Under Short-Circuit Faults: An Event-Triggered Model-Matching ApproachEnergies · 2026