Energies

Physics-Informed Machine Learning for UHVDC Transmission-Line Fault Identification: How Robust Is Near-Perfect Synthetic Accuracy to Simulation Fidelity?

Qiang Li, Yue Ma, Xinggu He, Shihong Zhang, Xianpeng Guo, Chenkai Zhang

Computational

Key points

From the paper's conclusion
  • We use two tiers: a physics-informed synthetic generator (620 samples, four channels, 100 kHz) and 181 reconstructions from a ±800 kV UHVDC system (two channels, 10 kHz), each from a real fault event.

Abstract

ML methods for UHVDC protection often report near-perfect accuracy on simplified simulations, yet their robustness to simulation fidelity is unclear. We use two tiers: a physics-informed synthetic generator (620 samples, four channels, 100 kHz) and 181 reconstructions from a ±800 kV UHVDC system (two channels, 10 kHz), each from a real fault event. On synthetic data, RF and XGBoost reach ≥99%, but direct transfer collapses to 44–54% accuracy with 75–100% false-alarm rates (original 50-case cohort). On the reconstructions, 47 features from the first 10 ms under family-aware group cross-validation give 55.1% balanced accuracy (95% CI 46.4–65.2; missed-detection 73.9%, false-alarm 15.8%)—far below the synthetic bound and far above the <5% requirement. Prior 70–76% and 74.8% estimates were inflated by scenario-family leakage and are not reproduced. Adding measured converter dynamics to the generator does not recover transfer (≈49.7%, 100% missed detection), so the gap is not a mean-trajectory effect alone. The strongest classical rule (dId/dt) reaches 62.1% balanced accuracy in-sample (56.6% out-of-sample) at 75.8% false-alarm rate; we claim no ML superiority, neither deployment-grade. Results are internal to one system with no independent test cohort or field validation, and are an honest benchmark of the fidelity gap, not a deployable solution.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Physics-Informed Machine Learning for UHVDC Transmission-Line Fault Identification: How Robust Is Near-Perfect Synthetic Accuracy to Simulation Fidelity? — Science Skim