Impact of Triplen Harmonics Generated by Modern Non-Linear Loads on Neutral Conductor Overheating in Low-Voltage Smart Buildings
Teodora Lazăr, Daria Ionescu, Dan Cristian Lazar, Florin Gabriel Popescu, Adina Milena Tătar, Georgeta Buică, Dragoș Păsculescu
Universitatea Din Petrosani · Constantin Brâncuși University of Targu Jiu
Key points
From the paper's conclusion- The rapid proliferation of single-phase non-linear loads, such as LED lighting and IT equipment, in modern Smart Buildings has introduced significant power quality challenges in low-voltage electrical installations.
Abstract
The rapid proliferation of single-phase non-linear loads, such as LED lighting and IT equipment, in modern Smart Buildings has introduced significant power quality challenges in low-voltage electrical installations. A critical but often underestimated consequence is the severe overloading of the neutral conductor caused by triplen harmonics (particularly the 3rd harmonic), which sum algebraically even in balanced three-phase systems. This paper analyzes the electrical and thermal impact of these distortions using a detailed MATLAB/Simulink model of a 400/230 V (3P + N) network. The simulation results demonstrate that under highly distorted conditions (Scenario S3), the neutral current can reach 180% of the nominal phase current (18 A vs. 10 A). Furthermore, the Joule losses analysis reveals a thermal stress more than three times higher on the neutral conductor (peak ~65 W) compared to the phase conductor (~20 W), challenging the traditional design practice of neutral undersizing. To address these safety issues, this study proposes a novel neutral-to-phase current ratio index (kN) and a proactive decision matrix for Building Management Systems (BMS). Unlike traditional mitigation strategies that rely on static hardware oversizing, passive filters, or specialized transformers, the proposed approach offers a dynamic, cost-effective, and software-driven solution that can be easily integrated into the existing automation infrastructure of modern Smart Buildings. The model identifies a critical tipping point at a 3rd harmonic content of 35.3%, where kN ≥ 1. By continuously monitoring the kN parameter, the proposed algorithm enables a transition from passive protection to active power management, triggering automated responses to prevent insulation degradation and mitigate fire hazards.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- A two-stage robust non-intrusive load monitoring method against unknown waveform distortionsScientific Reports · 2026
- Evaluation of Electromagnetic Performances of Three Parallel Cable Systems and a Busbar System Used in Power Distribution Network Under High THD Harmonic Loading with FEMEnergies · 2026
- Harmonic Distortion and Distribution Transformer Thermal Risk in Low-Voltage Networks: Feeder Impedance Sensitivity for Sustainable Renewable Energy IntegrationSustainability · 2026
- An IoT-based platform for electrical monitoring, load forecasting, and power quality disturbance detection in three-phase buildingsEnergy Informatics · 2026
- Power quality impact of residential LED loads under grid and isolated generator supplyElectrical Engineering · 2026
- Physics-Guided Multi-Output Surrogate Modeling of a Centralized-UPS Data CenterarXiv · 2026