HIL-based conformance testing: benchmarking IEC 61850 GOOSE transfer times across multi-vendor IEDs
Jhonatan Antônio Cassol, Leonardo de Freitas Silveira, Bruna Rafaela dos Santos Diana, João Pedro Scherer Cipriani, Mauricio Sperandio, Martin Wolter, Luiz Fernando Freitas-Gutierres, Adriano Peres de Morais
Key points
From the paper's conclusion- Results demonstrate that all evaluated equipment operated within normative transfer time limits, successfully satisfying the Gpf1/TT6 performance criteria and highlighting HIL simulation as a robust solution for testing automated power systems.
Abstract
The IEC 61850 standard is essential for interoperability of modern electrical substations. Its GOOSE protocol ensures high-speed transmission of critical events between intelligent electronic devices, which must comply with strict IEC 61850-10 transfer time requirements. This paper presents a hardware-in-the-loop virtual commissioning method for device conformance testing. Utilizing real-time simulation, a standardized “ping-pong method” test was implemented to monitor data traffic across multi-vendor devices. Performance was validated through 1,000 statistical trials per device in accordance with IEC 61850-10. Results demonstrate that all evaluated equipment operated within normative transfer time limits, successfully satisfying the Gpf1/TT6 performance criteria and highlighting HIL simulation as a robust solution for testing automated power systems.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- A Comprehensive Review of IEC 61850 Conformance Testing: Current Practices, Challenges, and Improvement OpportunitiesEnergies · 2026
- Virtual Commissioning of an IEC 61850-Based Substation Automation System Through an Integrated Engineering WorkflowB&H Electrical Engineering · 2026
- Review of recent developments in grid codes: Focus on compliance testing and grid-forming inverter-based resourcesRenewable and Sustainable Energy Reviews · 2025
- Grid-Compliance Testing of Wind Turbines through Virtualized Component Tests: Testing Concept and Test BencharXiv · 2026
- Risk–Observability Mismatch in an IEC 61850 Digital Substation: A Structured Cyber-Physical AssessmentApplied Sciences · 2026
- Study on the Basic Architecture and Decision Logic of an Add-On Advanced Adaptive Protection Relay Using IEC 61850IEEJ Transactions on Power and Energy · 2026