A real-time explainable machine learning framework for wide-area fault detection and localization using optimally placed synchrophasor measurements
Adedeji Adeyemi, Elijah Osunkentan, Artem Kashtanov, Martin Wolter
Key points
From the paper's conclusion- These results demonstrate that combining optimized PMU placement, real-time synchrophasor communication, and explainable machine learning enables fast, accurate, and transparent wide-area protection suitable for next-generation transmission systems.
Abstract
Modern transmission networks face increasing protection challenges due to renewable energy integration, bidirectional power flows, high-impedance faults (HIFs), and potential failures of local protection devices, motivating the development of intelligent wide-area protection schemes. This paper presents a distributed real-time framework for wide-area fault detection and localization using synchrophasor measurements. Optimal Phasor Measurement Unit (PMU) placement is achieved using Binary Integer Linear Programming (BILP) to ensure complete network observability with the minimum number of PMUs. A Virtual PMU implemented in the OPAL-RT HYPERSIM real-time simulator streams synchrophasor measurements via the IEEE C37.118 protocol over User Datagram Protocol (UDP) to a separate computer, where a multilayer Artificial Neural Network (ANN) and a Support Vector Machine (SVM) perform real-time inference for fault detection and faulted-line identification. The framework is evaluated on the IEEE 9-bus system under symmetrical, asymmetrical, and high-impedance fault conditions (up to 90 Ω in testing, 80 Ω in training). The ANN reaches 98.68 % ± 0.10 % test accuracy (mean ± SD, 5 training runs) with zero false positives; the SVM reaches 98.37 % ± 0.06 %. The estimated average inception-to-decision latency is ≈9.4 ms (8.33 ms average PMU frame-waiting time, ∼0.5 ms estimated communication/IEEE C37.118 processing, ∼0.5 ms estimated feature extraction, and 0.083 ms measured Artificial Neural Network (ANN) inference), with a worst-case PMU frame-waiting time of 16.67 ms at 60 frames/s well within the 50–150 ms fault duration range in the dataset. The trained models are not inherently topology-adaptive; however, topology-aware retraining on additional samples recovers both models to at least 98.7 % accuracy across all evaluated topology-change scenarios. SHapley Additive exPlanations (SHAP) analysis identifies current magnitude features at THE three PMU buses as the dominant fault-discriminating features, consistent with (though not an independent statistical proof of) the BILP placement strategy. These results demonstrate that combining optimized PMU placement, real-time synchrophasor communication, and explainable machine learning enables fast, accurate, and transparent wide-area protection suitable for next-generation transmission systems.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Machine Learning and Deep Learning Techniques for Fault Location in Transmission LinesApplied Sciences · 2026
- Hybrid CNN-decision tree framework for efficient transmission line fault detection and classification: an XAI-based approachScientific Reports · 2026
- A Hybrid Two-Stage Machine Learning Pipeline for Fault Detection and Classification in Power Transmission SystemsarXiv · 2026
- Quiet-State-Anchored Simulation-to-Reality Adaptation for Arcing High-Impedance Fault DetectionEnergies · 2026
- Fault identification and localization in transmission lines using an IVY-optimized generalized additive modelScientific Reports · 2026
- A Unified Online Assessment Framework for Pre-Fault and Post-Fault Dynamic SecurityEnergies · 2026