Research on partial discharge signal recognition and classification of power transformer based on acoustic-VMD and CNN-LSTM
Liang Chen, Wen You, Huaquan Su, Ke Xiong, D.-W. Chen
China Southern Power Grid (China)
Key points
From the paper's conclusion- This study proposes a novel hybrid Acoustic-VMD and CNN-LSTM model featuring: (1) sample entropy-optimized variational mode decomposition (automatically determining modes and penalty factor), (2) parallel 1D-CNN (5 layers and bidirectional LSTM (2 layers, 256 units) branches, and (3) hierarchical attention mechanisms (8 heads) for dynamic feature fusion.
Abstract
Partial discharge (PD) detection in power transformers is critical for preventing insulation failures in modern power grids, yet remains challenging due to signal complexity and environmental noise. Existing methods struggle with accurate PD classification under strong electromagnetic interference and varying load conditions. This study proposes a novel hybrid Acoustic-VMD and CNN-LSTM model featuring: (1) sample entropy-optimized variational mode decomposition (automatically determining modes and penalty factor), (2) parallel 1D-CNN (5 layers and bidirectional LSTM (2 layers, 256 units) branches, and (3) hierarchical attention mechanisms (8 heads) for dynamic feature fusion. Experimental results demonstrate superior performance with 96.2% classification accuracy for multi-source defects (38% improvement over wavelet methods), 5.8mm mean absolute localization error (53% better than TDOA), and consistent 4.2° angular accuracy under high noise, while maintaining practical 0.8s processing time. The research conclusively establishes that synergistic integration of adaptive signal processing and attention-based deep learning significantly advances PD diagnostics, achieving both computational efficiency and robust performance in complex operational environments.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Partial Discharge Detection and Localization in Power Transformers Using an Integrated Fiber‐Optic Acoustic Monitoring FrameworkJournal of Sensors · 2026
- Characteristics of Partial Discharge of Typical Defects in Converter Transformer Under OperationEnergies · 2026
- Physics-Guided Dual-Domain Transformer for Reliable Partial Discharge Recognition of Power Cable Insulation under Heterogeneous Acquisition ConditionsEngineering Research Express · 2026
- Optical fiber sensing and partial discharge fault diagnosis for power cable health monitoringMeasurement Science and Technology · 2025
- Advanced Signal Processing Methods for Partial Discharge Analysis: A ReviewSensors · 2025
- Research on the dimension reduction of the partial discharge feature space for oil-paper insulated power transformerScientific Reports · 2026