Characteristics of Partial Discharge of Typical Defects in Converter Transformer Under Operation
Yunpeng Tang, Yiming Hu, Hong Liu, Jian Liu, Hua Yu, Minghe Chi
Key points
From the paper's conclusion- Four typical insulation defects—turn-to-turn, spacer block, electrostatic ring, and tap changer—were modeled, with experiments conducted in a 35 kV transformer tank using pure AC and composite AC/DC voltages (1:1, 1:3, 1:5, 1:7 ratios).
Abstract
Converter transformers, operating in complex electric fields for extended periods, are prone to insulation degradation. To investigate partial discharge (PD) characteristics caused by internal insulation deterioration, this study developed an AC/DC PD simulation platform replicating real-world operating conditions. Four typical insulation defects—turn-to-turn, spacer block, electrostatic ring, and tap changer—were modeled, with experiments conducted in a 35 kV transformer tank using pure AC and composite AC/DC voltages (1:1, 1:3, 1:5, 1:7 ratios). The 48 Phase-Resolved Partial Discharge (PRPD) spectra were processed through image cropping, grayscale conversion, and dimension standardization, with 84% training and 16% testing datasets. Convolutional neural networks (CNNs) achieved an overall classification accuracy of 93.7% on the test set. Field validation using ±400 kV real-world converters confirmed the network’s precision in PD pattern recognition, providing technical support for insulation condition diagnosis and fault prediction in converter transformers.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Research on partial discharge signal recognition and classification of power transformer based on acoustic-VMD and CNN-LSTMPLoS ONE · 2025
- Research on the dimension reduction of the partial discharge feature space for oil-paper insulated power transformerScientific Reports · 2026
- Physics-Guided Dual-Domain Transformer for Reliable Partial Discharge Recognition of Power Cable Insulation under Heterogeneous Acquisition ConditionsEngineering Research Express · 2026
- A Study on the Identification of Partial Discharges in Typical Defects of Cross-Linked Polyethylene Cables Using the CNN-SE-RAP AlgorithmEnergies · 2026
- Partial discharge fault diagnosis method for metro dry-type transformers based on HHO-BiTCNJournal of Physics: Conference Series · 2026
- Toward Intelligent Power Transformer Diagnostics: From Multi-Source Condition Monitoring to Digital TwinsEnergies · 2026