Temperature-Field Reconstruction and Heat-Source Inversion Estimation Method for High-Voltage Switchgear Based Reduced-Order PINN Surrogate Model
Shengxue Tang, Xiang Zheng, Er-Peng Wang, Songyang Han, Yize Cheng
Key points
From the paper's conclusion- To address the difficulty in directly measuring internal heat sources, a fast three-dimensional temperature-field reconstruction, candidate heat-source identification, and heat-source power inversion method for high-voltage switchgear is proposed based on a reduced-order surrogate model integrating Proper Orthogonal Decomposition (POD) and physics-informed neural networks (PINNs).
Abstract
Localized overheating induced by poor electrical contact, loosened busbar connections, and insulation degradation is a major precursor to failures in high-voltage switchgear. To address the difficulty in directly measuring internal heat sources, a fast three-dimensional temperature-field reconstruction, candidate heat-source identification, and heat-source power inversion method for high-voltage switchgear is proposed based on a reduced-order surrogate model integrating Proper Orthogonal Decomposition (POD) and physics-informed neural networks (PINNs). First, a coupled three-dimensional thermal–flow coupled computational fluid dynamics(CFD) model is established to generate temperature fields under different heat-source conditions. POD is then applied to extract the dominant thermal modes and their corresponding low-dimensional modal coefficients from the high-dimensional temperature fields. A PINN-based reduced-order surrogate model is subsequently trained to establish the nonlinear mapping from heat-source parameters to POD modal coefficients, while residuals of the steady-state heat conduction equation and boundary-condition constraints are incorporated into the loss function to enforce physical consistency and enhance prediction accuracy. Based on external temperature measurements, an Improved Grey Wolf Optimizer (I-GWO) is further adopted to identify the active fault heat source from a predefined set of candidate locations and inversely estimate its corresponding heat-source power. Numerical simulations and temperature-rise experiments show that the proposed method accurately reconstructs the three-dimensional temperature distribution and identifies local high-temperature regions. In the temperature-rise experiment, the relative error of heat-source power inversion is only 2.27%, demonstrating that the proposed framework enables rapid and accurate temperature-field reconstruction and heat-source inversion.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- A Review of Physics-Informed and Data-Driven Surrogate Models for Power Transformer Fault Diagnosis.Sensors (Basel, Switzerland) · 2026
- Simulation-Based Ampacity Assessment of Cable Joints Based on Hotspot-Temperature InversionElectronics · 2026
- Research on digital twin diagnosis model for the thermal-electric field of high-voltage switchgearsScientific Reports · 2025
- Three-Parameter Steady-State Temperature-Rise Prediction for a 12 kV Ring Main Unit Using POD and Gaussian Process RegressionElectronics · 2026
- A Spatiotemporal Transformer–ConvLSTM Surrogate with Condition Embedding for Dynamic Three-Dimensional Temperature Field Prediction of XLPE HVDC CablesAutomation · 2026
- Interpretable surrogate modeling for load-aware thermal risk assessment of bolted switchgear busbar joints using electro-thermal simulationFrontiers in Mechanical Engineering · 2026