  • Thermal-risk assessment of bolted busbar joints is complicated by the coupled effects of electrical loading, contact condition, and heat dissipation.

Abstract

Thermal-risk assessment of bolted busbar joints is complicated by the coupled effects of electrical loading, contact condition, and heat dissipation. This study develops an interpretable forward-surrogate framework based on three-dimensional electro-thermal finite-element simulation. Physics enters through finite-element generation of the training data, physically defined input variables, and post hoc consistency checks, rather than through constraints embedded in the learning algorithm. Five prescribed inputs were considered: load current, contact resistance, effective contact ratio, ambient temperature, and convective heat-transfer coefficient. The effective-contact heating power was checked against P ≈ I 2 R c , with a maximum relative deviation of 0.173% across 400 simulated cases; 382 cases were retained within the intended applicability domain. Four candidate models were compared using 5 × 10 repeated cross-validation. The XGBoost regressor achieved R 2 = 0.990 ± 0.005 , R M S E = 1.877 ± 0.542 , and M A E = 1.042 ± 0.198 K , with performance comparable to random forest. For four-class simulation-oriented thermal-risk classification, XGBoost achieved an accuracy of 0.938 ± 0.026 and a macro F1-score of 0.941 ± 0.033 . SHapley Additive exPlanations (SHAP) analysis identified load current and prescribed contact resistance as the dominant contributors, while convection, ambient temperature, and effective contact ratio produced smaller, condition-dependent effects. The lower global importance of effective contact ratio reflects the area-averaged temperature-rise target and does not imply that current constriction is physically unimportant. Across three threshold schemes, all out-of-fold errors were between adjacent classes. The framework is geometry-specific and has not been experimentally validated. It predicts internal effective-contact temperature rise; relating this quantity to infrared surface measurements requires further validation.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers