Electronics

Three-Parameter Steady-State Temperature-Rise Prediction for a 12 kV Ring Main Unit Using POD and Gaussian Process Regression

Yongqin Lan, Xumei Lan, Jiaqi Yu, Wanting Wang, Lan Jiang, Gaoyi Ouyang, Junhui Wu

Key points

From the paper's conclusion
  • This study combines volume-weighted proper orthogonal decomposition (POD) with Gaussian process regression (GPR) to predict steady-state temperature-rise fields from current and two independent contact-resistivity multipliers.

Abstract

Repeated three-dimensional multiphysics solutions make temperature-rise analysis across ring main unit operating conditions computationally expensive. This study combines volume-weighted proper orthogonal decomposition (POD) with Gaussian process regression (GPR) to predict steady-state temperature-rise fields from current and two independent contact-resistivity multipliers. The database contains 187 simulated conditions. POD rank and coefficient mapping are selected using validation maximum-temperature-rise error, with multilayer perceptron and radial basis function methods as comparators. The selected 32-mode POD–GPR model achieves mean relative errors of 0.0039% for maximum temperature rise and 0.0100% for the full field on the in-domain test set. At 1250 A peak current, the mean absolute relative GPR-to-simulation error across ten temperature-rise groups is 0.00697%. The corresponding simulation-to-experiment and GPR-to-experiment errors are 2.7600% and 2.7595%. The median full-field prediction and reconstruction time is 0.016033 s. The model enables rapid steady-state temperature-rise calculation within the investigated parameter domain.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers