Three-Parameter Steady-State Temperature-Rise Prediction for a 12 kV Ring Main Unit Using POD and Gaussian Process Regression
Yongqin Lan, Xumei Lan, Jiaqi Yu, Wanting Wang, Lan Jiang, Gaoyi Ouyang, Junhui Wu
Key points
From the paper's conclusion- This study combines volume-weighted proper orthogonal decomposition (POD) with Gaussian process regression (GPR) to predict steady-state temperature-rise fields from current and two independent contact-resistivity multipliers.
Abstract
Repeated three-dimensional multiphysics solutions make temperature-rise analysis across ring main unit operating conditions computationally expensive. This study combines volume-weighted proper orthogonal decomposition (POD) with Gaussian process regression (GPR) to predict steady-state temperature-rise fields from current and two independent contact-resistivity multipliers. The database contains 187 simulated conditions. POD rank and coefficient mapping are selected using validation maximum-temperature-rise error, with multilayer perceptron and radial basis function methods as comparators. The selected 32-mode POD–GPR model achieves mean relative errors of 0.0039% for maximum temperature rise and 0.0100% for the full field on the in-domain test set. At 1250 A peak current, the mean absolute relative GPR-to-simulation error across ten temperature-rise groups is 0.00697%. The corresponding simulation-to-experiment and GPR-to-experiment errors are 2.7600% and 2.7595%. The median full-field prediction and reconstruction time is 0.016033 s. The model enables rapid steady-state temperature-rise calculation within the investigated parameter domain.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Temperature-Field Reconstruction and Heat-Source Inversion Estimation Method for High-Voltage Switchgear Based Reduced-Order PINN Surrogate ModelEngineering Research Express · 2026
- A Spatiotemporal Transformer–ConvLSTM Surrogate with Condition Embedding for Dynamic Three-Dimensional Temperature Field Prediction of XLPE HVDC CablesAutomation · 2026
- Probabilistic Operating-Error Forecasting for 10 kV Instrument Transformers Using Intrinsic Variation–Trend Decomposition and Multi-Kernel Deep Gaussian ProcessesElectronics · 2026
- Research on the Data‐Driven Fast Calculation Method of the Temperature Field Distribution of Valve‐Side RIP Bushing Used in UHV DC Converter TransformerHigh Voltage · 2025
- GridForge: An Open Physics-Informed Digital Twin and Benchmark Suite for UK 11 kV Underground Distribution CablesarXiv · 2026
- Application of Digital Twins to Overhead Line ConductorsMetrology · 2026