Proxy-Based Identification of Heating, Ventilation, and Air-Conditioning-Related Carbon Emission Drivers in Commercial Building Energy Operation

Jiahui Zhu, Junqi Yu, Meng Zhou

Key points

From the paper's conclusion
  • This study investigates phase-dependent HVAC-related carbon emission drivers in a large shopping mall using 23 monthly observations of energy consumption and meteorological data from February 2021 to December 2022.

Abstract

Energy conservation and carbon reduction in commercial buildings are essential for achieving carbon neutrality targets, but carbon emission drivers may change under operational disruptions. This study investigates phase-dependent HVAC-related carbon emission drivers in a large shopping mall using 23 monthly observations of energy consumption and meteorological data from February 2021 to December 2022. To avoid mechanical overlap between total electricity consumption and HVAC-related carbon emissions, non-HVAC electricity consumption was constructed as a proxy for operational intensity. Four progressive regression models were developed, including a temperature-only baseline model, a proxy-augmented model, a phase-dummy model, and a phase-interaction model. The results show that the phase-interaction model achieved the best in-sample explanatory performance, with the adjusted R² increasing from 0.3705 to 0.9641 and the RMSE decreasing from 231.2226 to 49.7036 compared with the temperature-only model. The marginal effect of temperature increased from 10.3703 in the restricted phase to 26.0975 in the recovery phase, indicating a stronger temperature–HVAC carbon emission association during the recovery phase. Robustness analyses using residual diagnostics, HC3 robust standard errors, leave-one-month-out sensitivity analysis, leave-one-out cross-validation, expanding-window time-series validation, and phase-stratified bootstrap resampling supported the stability of the temperature–phase interaction, although the simpler phase-dummy model showed better strictly chronological predictive performance than the interaction model. In contrast, the non-HVAC electricity proxy and its phase interaction were not statistically significant under HC3 robust inference, indicating that the proxy-related associations were less robust and should be interpreted cautiously. The proposed framework is intended for retrospective carbon accounting and exploratory driver identification in data-constrained commercial buildings, rather than real-time HVAC control or peak-load forecasting.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers