Temperature Associations of Paired Cooling and Electricity Coincidence in Eight Building Portfolios
Umur Özbek, Dilek Yasar, Fatih Kariptaş, Füsun Seçer Kariptaş
Key points
From the paper's conclusion- We compared within-calendar temperature slopes of daily thermal-cooling and electricity coincidence factors (CFs) using paired hourly meter records from 420 buildings in eight source-defined portfolios across two public archives.
Abstract
Previous studies have characterized building peak-load diversity and temperature-sensitive demand, but it remains unclear whether the temperature association of electricity coincidence also describes that of thermal cooling in the same buildings. This distinction matters for interpreting aggregate portfolio peaks and their timing. We compared within-calendar temperature slopes of daily thermal-cooling and electricity coincidence factors (CFs) using paired hourly meter records from 420 buildings in eight source-defined portfolios across two public archives. The analysis comprised 2853 cooling and 2852 paired portfolio-days; year–month- and weekday-adjusted portfolio regressions were synthesized with random-effects models. Per +5 °C, the pooled cooling-CF slope was +0.912 percentage points (95% Hartung–Knapp confidence interval [CI], +0.330 to +1.494), whereas the directly estimated cooling-minus-electricity slope contrast was +0.803 points (95% CI, +0.353 to +1.252). Both prediction intervals crossed zero, indicating potential variation in portfolio-specific responses. Peak-hour alignment remained inconclusive under alternative definitions, while the concurrent high-load share at the 90% threshold had a pooled slope of +3.491 points (95% CI, +1.608 to +5.374). Across the eight analyzed portfolios, the matched-carrier comparison supports a positive average cooling-minus-electricity temperature-slope contrast, while aggregate coincidence and individual peak-hour alignment remain distinct measures of portfolio peak behavior.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Temporal resolution matters: Evaluating carbon emission factors for accurate accounting in commercial buildingsApplied Energy · 2026
- Proxy-Based Identification of Heating, Ventilation, and Air-Conditioning-Related Carbon Emission Drivers in Commercial Building Energy OperationEngineering Research Express · 2026
- Calibration of urban building energy model using smart meter data for district peak load predictionApplied Energy · 2026
- Data-driven analysis of building thermal performance using room-level thermal time constantsE3S Web of Conferences · 2026
- A refined theoretical method for reducing overestimation in building-level design cooling load derived from temporal misalignment of room-level design cooling loadsResults in Engineering · 2026
- Understanding energy flexibility in buildings: A sensitivity analysis of building characteristics and thermal storage potentialEnergy and Buildings · 2026