Heat pump–based recovery of low-temperature waste heat from a datacenter: A multi-scenario assessment of integration into an existing district heating network
Chiara Monzani, Giulio Cerino Abdin, Alberto Poggio, Luca Degiorgis, Giulia Montanari
Key points
From the paper's conclusion- The results indicate that supplying the low-temperature swimming pools yields the highest system efficiency, achieving a COP of 4.28 and enabling the utilisation of approximately 75% of the available waste heat.
Abstract
The integration of low-temperature waste heat into district heating and cooling (DHC) networks represents a promising strategy for improving overall system efficiency and accelerating the decarbonization of urban energy infrastructures. This study presents a techno-economic assessment of waste heat recovery from an existing air-cooled data center, where cooling is provided through a chilled-water loop operating between 9 and 11 °C. The facility is located within a building connected to an 80 °C district heating subnetwork supplied by a 120 °C primary network and is situated in close proximity to low-temperature heat consumers, namely public swimming pools, whose chlorinated-water heat exchangers can be supplied at approximately 45 °C. Waste heat is recovered and upgraded through a water-to-water heat pump to meet the temperature requirements of the considered end uses. An hourly simulation model developed in Python was employed to evaluate system performance, using demand profiles reconstructed from monitoring data, including a dedicated measurement campaign conducted at the swimming-pool substation. Three alternative recovery strategies were investigated: (i) heat injection exclusively into the 80 °C district heating subnetwork, (ii) direct supply to the 45 °C swimming pools, and (iii) a hybrid configuration serving both temperature levels through the integration of an additional booster heat pump. The analyzed configurations were compared in terms of recovered and delivered thermal energy, electricity consumption of the heat pumps, overall system coefficient of performance (COP), including auxiliary loads, levelised cost of heat (LCOH), and simple payback period. The results indicate that supplying the low-temperature swimming pools yields the highest system efficiency, achieving a COP of 4.28 and enabling the utilisation of approximately 75% of the available waste heat. Conversely, the hybrid configuration maximizes heat recovery, increasing source utilization to 93% while providing greater operational flexibility. Across the investigated scenarios, the simple payback period ranges from 3.4 to 10 years, whereas the LCOH varies between 62 and 101 €/MWh. Overall, the findings confirm the potential of data centers as reliable and continuous urban waste-heat sources and provide quantitative insights for the design and optimization of integrated district energy systems.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Smart Reuse of Waste Heat from Data Centres: Energy and Exergy Analysis for a District-Heating Network in BulgariaEnergies · 2026
- Maximizing waste heat recovery from a building-integrated edge data centerScientific Reports · 2025
- Assessing low temperature waste heat integration in 5th generation district heating and cooling: a case study evaluationEnergy and Buildings · 2026
- From servers to services: modeling data centers as heat-active urban energy prosumersApplied Energy · 2025
- Electricity-computility integration of data centers and pumped storage driven by cold energy storage in ChinaEnergy Reports · 2025
- Modelling of district heating return water usage in apartment buildingsE3S Web of Conferences · 2026