Smart Reuse of Waste Heat from Data Centres: Energy and Exergy Analysis for a District-Heating Network in Bulgaria
Antonio Verzino, Lorenzo Talluri, Andrea Rocchetti, Luca Socci
University of Florence
Key points
From the paper's conclusion- These findings show that data centres can act as reliable thermal assets for existing district-heating networks, with heat pumps and thermal energy storage emerging as key enablers for district-heating decarbonisation.
Abstract
The rapid growth of data centres is driving higher electricity consumption and continuous generation of low-grade waste heat. Integrating this heat into district-heating networks offers a smart strategy for thermal management in urban areas. In this context, this study presents an energy and exergy analysis of an integrated system comprising a data centre, vapour-compression heat pumps, thermochemical energy storage, and a third-generation district-heating network in Varna (Bulgaria). The proposed system relies on data-centre waste-heat recovery via vapour-compression heat pumps and thermochemical energy storage, enabling seasonal decoupling between heat availability and demand. Despite the relatively small size of the data centre (500 kW) compared to the district-heating system (average thermal demand of 9.3 MW), recovered waste heat can supply up to 3.0% of the annual heat demand and over 20% of the instantaneous load. The integrated configuration consistently improves overall exergy efficiency, confirming its thermodynamic advantage. These findings show that data centres can act as reliable thermal assets for existing district-heating networks, with heat pumps and thermal energy storage emerging as key enablers for district-heating decarbonisation.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Heat pump–based recovery of low-temperature waste heat from a datacenter: A multi-scenario assessment of integration into an existing district heating networkJournal of Physics: Conference Series · 2026
- From servers to services: modeling data centers as heat-active urban energy prosumersApplied Energy · 2025
- Energy, Exergy, Economic, Environment Analysis and Multiobjective Optimization of the Organic Rankine Cycle Integrating an Absorption Heat Transformer Driven by Geothermal Energy for Data Center Power Supply and Waste Heat Recovery.ACS omega · 2026
- Decarbonization strategies in district heating systems: the A2A integrated modelJournal of Physics: Conference Series · 2026
- Planning Waste-to-Energy-Coupled AI Data Centers Through Grade-Matched Cooling and Corridor ScreeningThermo · 2026
- Peak load provision in district heating networks: a survey on the status quo and decarbonisation optionsEnergy · 2026