Maximizing waste heat recovery from a building-integrated edge data center
Mustafa Kuzay, Ender Demirel, Cagatay Yilmaz, Binod Prasad Koirala, Philipp Heer
Eskisehir Technical University · RISE Research Institutes of Sweden
Key points
From the paper's conclusion- Numerical simulations conducted using the validated CHT model show that the MOTA can improve heat recovery by up to 17.1% under various IT loads.
Abstract
Small data centers can be integrated into the energy systems of commercial and tertiary buildings to capture waste heat generated by servers, mitigate environmental impacts and enhance energy efficiency. This study introduces a novel methodology for maximizing waste heat capture from the cooling coils by optimizing workload distribution in an edge data center consisting of air-cooled servers. The maximization of outlet temperatures algorithm (MOTA) was developed using a validated fast thermal evaluation approach. Experimental studies were conducted to characterize parameters of the cooling system such as air and water flow rates and effectiveness of the coil. A multi-region conjugate heat transfer (CHT) numerical model was developed to demonstrate feasibility of the proposed approach. Heat transfer through the cooling coil was numerically modeled using the effectiveness-NTU method. Good agreement was achieved between the simulated and measured water temperatures at the outlet of the cooling coil. Numerical simulations conducted using the validated CHT model show that the MOTA can improve heat recovery by up to 17.1% under various IT loads. Furthermore, optimizing the water flow rate can reduce the cooling load by up to 53.2%. These combined results highlight the potential of the proposed algorithm for energy-efficient management of data centers. Computational cost and real-world applicability of the proposed algorithm were discussed in detail.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Heat pump–based recovery of low-temperature waste heat from a datacenter: A multi-scenario assessment of integration into an existing district heating networkJournal of Physics: Conference Series · 2026
- From servers to services: modeling data centers as heat-active urban energy prosumersApplied Energy · 2025
- Operational analysis of the cooling system in a direct liquid-cooled data center: a measurement and simulation study on the impact of supply water temperatureApplied Energy · 2025
- Energy and carbon savings in data centres through liquid-to-chip cooling with differential temperature controlAdvances in Applied Energy · 2026
- Smart Reuse of Waste Heat from Data Centres: Energy and Exergy Analysis for a District-Heating Network in BulgariaEnergies · 2026
- Holistic energy analysis method for thermal management architectures of data centersInternational Journal of Heat and Mass Transfer · 2026