Journal of Physics: Conference Series

Design optimization study on a nozzle for the local application of high-boiling-point extinguishing agent

Qingsong Zhao, Jianqin Ma, Zhichao Hua

Key points

From the paper's conclusion
  • Based on the test results, the K100 nozzle is established as the optimal model, and the design criteria and optimization directions for nozzles are proposed.

Abstract

Perfluorohexanone, as a novel, highly efficient, and clean high-boiling-point gaseous extinguishing agent, is a liquid under normal temperature and pressure (boiling point 49.2 °C), requiring mechanical atomization to form an aerosol mist field for fire extinguishing. Its spray morphology and atomization characteristics determine the extinguishing effect, necessitating specialized nozzle design. Focusing on the 70B pool fire and 2A wood crib fire models, this paper conducts systematic fire extinguishing tests and comparative analysis on single-orifice nozzles, multi-orifice nozzles, and optimized series nozzles based on previous research results on key parameters and safety thresholds for local application. Based on the test results, the K100 nozzle is established as the optimal model, and the design criteria and optimization directions for nozzles are proposed. This study provides a direct experimental basis for the engineering development of nozzles for the local application of high-boiling-point extinguishing agents.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Design optimization study on a nozzle for the local application of high-boiling-point extinguishing agent — Science Skim