Study on the Effectiveness of Perfluorohexanone in Extinguishing Small-Scale Pool Fires in Enclosed Compartments Under Low-Pressure Conditions
Quanyi Liu, Ruxuan Yang, Pei Zhu
Civil Aviation Flight University of China · Nanjing University of Aeronautics and Astronautics
Key points
From the paper's conclusion- The results show that the weight coefficient for chemical inhibition intensity is as high as 38.81, significantly exceeding other factors, demonstrating that perfluorohexanone primarily relies on chemical inhibition to interrupt the combustion chain reaction.
Abstract
To investigate the fire suppression effectiveness of perfluorohexanone in low-pressure environments, a self-built fire suppression experimental platform was utilized to analyze the influence of ambient pressure and heat release rate on its performance. The results demonstrate that under normal-pressure conditions, the extinguishing time increases with the heat release rate of the fire source, whereas under low-pressure conditions, the extinguishing time decreases as the heat release rate increases. Specifically, under normal pressure, the extinguishing times for Fire Pan A (10 cm × 10 cm × 10 cm), Fire Pan B (15 cm × 15 cm × 10 cm), and Fire Pan C (20 cm × 20 cm × 10 cm) were 5.03 s, 8.15 s, and 9.63 s, respectively. In contrast, under low pressure, the extinguishing times were significantly shorter, with reductions of 2.8 s, 6.59 s, and 8.45 s, respectively. In terms of temperature reduction, the flame temperature decreased by approximately 300 °C under normal pressure, while under low pressure, it decreased by only about 100 °C. The concentration of hydrogen fluoride (HF) produced after extinguishment was relatively low, indicating limited toxicity. The HF concentration under normal pressure was, on average, approximately 59.2% higher than that under low-pressure conditions. Based on parameters such as the mass of the extinguishing agent, temperature changes, and hydrogen fluoride content, a fire suppression effectiveness model was established. The results show that the weight coefficient for chemical inhibition intensity is as high as 38.81, significantly exceeding other factors, demonstrating that perfluorohexanone primarily relies on chemical inhibition to interrupt the combustion chain reaction. This conclusion provides an important theoretical basis for the design and optimization of fire suppression systems in low-pressure environments such as aviation and high-altitude areas.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Design optimization study on a nozzle for the local application of high-boiling-point extinguishing agentJournal of Physics: Conference Series · 2026
- Molecular dynamics simulation of perfluorohexanone-based synergistic gas mixtures and mechanistic prediction of hydrogen fluoride formation pathways.Journal of molecular modeling · 2026
- The Effects of E-CF3-CH=CClH Addition on the Yield of Corrosive HF Gas During Thermal Pyrolysis of C6F12O AgentFire · 2026
- Analysis of ventilation effect on pool fire combustion at different scalesJournal of Physics: Conference Series · 2026
- Synthesis and Fire Suppression Performance of Thermosensitive Microelncapsulated Cis‐Hexafluoro‐2‐ButeneJournal of Vinyl and Additive Technology · 2026
- Experimental Study on Methane Explosion Suppression in Pipelines by Mixed Systems of Inert Gases (CO2/N2) and HFC-227ea.ACS omega · 2026