Wind-induced reliability assessment of a corroded angle-steel transmission tower
Linlin Zhang, Keji Chen, Rong Bian, Miaosong Gu, Haiwei Xu
Key points
From the paper's conclusion- The results show that with increasing corrosion depth, the reliability index of diagonal members, which are characterized by smaller thickness, declines faster than that of main members, which are characterized by larger thickness.
Abstract
This study presents a reliability assessment of a corroded angle-steel transmission tower. Corrosion depth was modelled by reducing the thickness of angle steel members. Performance functions for structural members were formulated according to code DL/T 5154-2012 and mechanical analysis. Subsequently, the effects of initial angle-steel thickness, slenderness ratio, and wind load return period on the reliability indices of Q345 and Q420 steel members are examined, and threshold reliability indices for diagonal and main members are established. Then, the critical corrosion depth of the transmission tower is analysed according to the code-based and mechanical analysis-based reliability indices. The results show that with increasing corrosion depth, the reliability index of diagonal members, which are characterized by smaller thickness, declines faster than that of main members, which are characterized by larger thickness. The reliability thresholds for diagonal and main members are 2.48 and 2.52, respectively. A corrosion depth of 1.0 mm, at which the reliability index of a diagonal member at the tower’s mid-height drops to the threshold of 2.48, is taken as the critical corrosion depth. Diagonal members are the critical members governing the corrosion resistance of transmission towers. Therefore, corrosion-resistant design should prioritize diagonal members with smaller initial thicknesses.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Ductility-Based Stiffness Optimization of Transmission Tower–Line Systems for Wind-Induced Collapse ResistanceProcesses · 2026
- Stability analysis of transmission towers in loess regions under wind and rain loadsJournal of Physics: Conference Series · 2026
- An Efficient Fatigue Life Estimation Procedure for Historical Steel Towers: A Case Study of the Riga TV TowerBuildings · 2026
- Dynamic Wind Loads on Double-Span Conductors and Their Influencing Factors: An Investigation Using Aeroelastic Wind Tunnel Tests and Finite Element AnalysisCivilEng · 2026
- Research on Wind-Induced Fatigue of Substation Disconnect Switchgear StructuresEnergies · 2026
- Research on corrosion detection criteria for tower grounding grids based on corrosion characteristics and magnetic field responseJournal of Physics: Conference Series · 2026