Research on Wind-Induced Fatigue of Substation Disconnect Switchgear Structures
Xiao Zhu, Peng Li, Qianbo Xiao, Min Liu, Shidong Nie, Qian Liu, Ze Wang, Qingshan Yang,
Key points
From the paper's conclusion- The results show that the windward and leeward M16 bolts at the flange joint suffer fatigue failure within the 50-year design service life.
Abstract
Substation pillar-type switchgear structures are important electrical equipment in the power transmission and transformation system. These structures are characterized by a large top mass, low overall stiffness, and low natural vibration frequency, and are prone to fatigue damage under long-term wind loads. At present, studies on wind-induced vibration fatigue of substation disconnect switch structures are relatively limited. In this paper, a numerical model of the substation disconnect switch structure is established on the basis of static tests, and wind loads are determined according to wind tunnel test results. The Weibull distribution model and the mixed distribution model (Weibull distribution + GPD distribution) are adopted to characterize the wind-speed probability distributions in large-scale steady strong-wind regions and typhoon-prone regions, respectively. Fatigue damage calculation and life prediction are carried out for the fatigue-critical positions of the disconnect switch structure. The results show that the windward and leeward M16 bolts at the flange joint suffer fatigue failure within the 50-year design service life. In large-scale steady strong-wind regions, the predicted fatigue lives of the critical M16-① and M16-⑤ bolts are 8.28 years and 8.48 years, respectively; in typhoon-prone regions, their predicted fatigue lives reduce to 0.87 years and 3.01 years, respectively. The research findings can provide a reference for the anti-fatigue design of flange joints for substation disconnect switch structures.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- An Efficient Fatigue Life Estimation Procedure for Historical Steel Towers: A Case Study of the Riga TV TowerBuildings · 2026
- Conditional Root-Stress Exceedance of a 220 kV Disconnect Switch Under Dynamic Slurry–Boulder Debris-Flow LoadingApplied Sciences · 2026
- Aerodynamic Flow Field and Mechanical Response of a Quad-Bundle Conductor–Stockbridge Damper System Under Sustained Wind LoadingApplied Sciences · 2026
- Meta-model-based fatigue analysis of 25 MW offshore jackets: relevance of wind and wave conditionsOcean Engineering · 2026
- Dynamic Response of Ice-Shedding Jump of Iced Quad-Bundled Conductors Under Ice–Wind Coupling EffectsEnergies · 2026
- Frequency-Dependent Cable Modeling for Power-Loss and Voltage-Drop Assessment in Wind Farm Collection Networks: A Tehuantepec Case StudyElectricity · 2026