Thermal Performance Enhancement of a Heat Pipe Heat Exchanger with an Internally Helical-Finned Condenser (HPHIC) using CFD Model for HVAC Application

Zahraa S. Abdzaid, Adel A. Eidan

Key points

From the paper's conclusion
  • The results show the potential application of this long-term internal helical fin as a passive modification on the condenser side and an understanding of the framework for evaluating an internally enhanced thermosyphon heat exchanger for the heat-recovery application in HVAC systems.

Abstract

Enhancement of condenser side heat rejection is essential for the improvement of the thermal performance of the gravity-assisted thermosyphon heat-pipe heat exchangers which are employed in passive heat recovery used in heating, ventilation, and air-conditioning (HVAC) systems. In this study, the performance of an otherwise identical smooth-wall condenser (SM) is compared to the performance of a passive condenser-enhancement concept which incorporates a continuous helical fin (HF) inside the condenser section, in a quantitative manner. ANSYS Fluent, a 3D CFD simulation software, was used to simulate the inlet-air temperature between 303 and 318 K and inlet-air velocity of 0.5 and 2.5 m s-1. In order to evaluate the effect of the modification of the internal condenser, the same two-row thermosyphon configuration with the same external aluminium fins were used for both cases, and the same operating conditions were applied. The numerical results showed a constant thermal advantage for the HF configuration with a condenser heat flux about 13.2% higher compared to the SM configuration under the investigated conditions. The heat flux was found to be 1304.53 W nr 2 when the air velocity was 0.5 m s −1 and 2684.41 W m −2 at 2.5 m s −1 in SM, whereas, for the HF, the heat flux was found as 1476.73 W m −2 at 0.5 m s −1 air velocity and 3038.75 W m −2 at 2.5 m s −1 air velocity, respectively, which is an increase of about 105.8% in both cases. In the same velocity range, the difference between the heat-flux of the helical-fin condenser and the heat-flux of the SM increased from 172.20 to 354.34 W/m 2 , showing that this thermal benefit of the helical-fin condenser was maintained with increasing air-side convective transport. Notably, a marginal difference in the mean condenser-wall temperature was obtained in the cases of SM and HF, and the mean condenser-wall temperatures of approximately 341.86 K and 341.88 K were predicted at 303 K and 0.5 m s-i, with the difference in the heat fluxes being around 13.2%. This behaviour suggests that the enhancement of the HF response is not only due to the increase of the wall temperature but also to the change of the internal condenser heat pathway which is linked to the two-phase transport and the additional wetted surface. Important, it is found that there is need to separate the surface-area based enhancement from the thermo-hydrodynamic based effect induced by the topology of internally enhanced thermosyphon condensers. The results show the potential application of this long-term internal helical fin as a passive modification on the condenser side and an understanding of the framework for evaluating an internally enhanced thermosyphon heat exchanger for the heat-recovery application in HVAC systems.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers