The thermo-fluid and exergy analysis of a shell and twisted helical tube heat exchanger
Mahmoud Abdelmagied
Helwan University
Key points
From the paper's conclusion- The effects of the twisted helical coil diameter ( D ), inner Reynolds number ( Re i ), and shell Reynolds number ( Re sh ) on the thermal performance ( η ) and exergy characteristics of the STHTHX are examined and compared with those of a conventional shell and smooth helical tube heat exchanger ( SSHTHX ).
Abstract
Abstract The present study experimentally investigates a shell and twisted helical tube heat exchanger ( STHTHX ), which employs a twisted helical tube configuration to enhance thermofluid performance under turbulent flow conditions. The effects of the twisted helical coil diameter ( D ), inner Reynolds number ( Re i ), and shell Reynolds number ( Re sh ) on the thermal performance ( η ) and exergy characteristics of the STHTHX are examined and compared with those of a conventional shell and smooth helical tube heat exchanger ( SSHTHX ). The twisted helical tube design is expected to intensify the swirl motion of the fluid and induce additional flow disturbances and improve the thermofluid characteristics. Three test specimens were fabricated and tested with twisted coil diameters ( D ) of 0.095, 0.125, and 0.165 m. The experiments were carried out under counter-flow conditions with inner mass flow rates ( ṁ i ) ranging from 0.033 to 0.181 kg/s, corresponding to Reynolds numbers ( Re i ) from 6.1 × 10 3 to 4.4 × 10 4 in the twisted helical coil, and shell-side mass flow rates ( ṁ sh ) between 0.067 and 0.175 kg/s. This study aims to fill the research gap regarding the thermofluid characteristics and exergy analysis of the STHTHX and to provide experimental guidance for its design and optimization. The results reveal that the STHTHX demonstrated superior thermofluid performance compared to SSHTHX . Reducing the twisted coil diameter from 0.165 to 0.095 m increasing $$\overline{{Nu_{i} }}$$ , and f i by 47.9, and 38.77%, respectively. The STHTHX achieved a maximum η of 2.07 at D = 0.095 m. New correlations are proposed to predict $$\overline{{Nu_{i} }}$$ and f i .
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Fluid and thermal flow in annular side of the double twisted helically coiled tubes heat exchangers under various configurationsInternational Journal of Air-Conditioning and Refrigeration · 2025
- Thermohydraulic behavior of the triple helical tube with corrugated tube configurationsDiscover Applied Sciences · 2026
- Heat Transfer Enhancement in a Concentric Tube Heat Exchanger Using Dual‐Side Helical Wire Coil Inserts: A Numerical Study With Experimental ValidationHeat Transfer · 2026
- Improving the Thermofluid Performance of a Shell and Corrugated Coil Heat Exchanger With Novel ConfigurationsJournal of Thermal Science and Engineering Applications · 2026
- A novel integrated approach to heat transfer enhancement using baffles and inner fins in helical coil heat exchangersCase Studies in Thermal Engineering · 2025
- Passive Techniques for Heat Transfer Enhancement in Selected Industrial Heat Exchangers: A Comprehensive Review of Geometric Modifications and NanofluidsThermo · 2026