The effect of ventilation system demand response and unobtained comfort cooling on indoor temperatures in office buildings

Sandra Boström, Annica Nilsson, Samuel Wennlund, Tobias Bergman

Key points

From the paper's conclusion
  • The results show that even short reductions of 15 minutes can lead to uncomfortable temperatures, especially in sun-exposed or densely occupied areas.

Abstract

More intermittent energy production and increasing electricity demand poses new challenges for the power grid. Demand response, DR, in buildings has the potential to be part of the solution. This study investigates the potential of using the ventilation system in a timber-framed office building to contribute to DR by reducing airflow during selected periods. Using building energy simulations, three ventilation reduction scenarios were analyzed in varying weather conditions. The results show that even short reductions of 15 minutes can lead to uncomfortable temperatures, especially in sun-exposed or densely occupied areas. With a seasonally adapted ventilation reduction strategy, up to one hour ventilation reductions are generally possible while still maintaining an acceptable indoor climate. The power-saving potential varies between 0 and 15 kW for the scenarios that meet the European indoor-climate standards. The study concludes, that the thermal indoor environments of office buildings are sensitive to ventilation reductions. Additionally, the benefits to the power grid of ventilation-based DR are modest.