Operating-envelope assessment of static-pressure reset control in VAV systems
Iven Suykens, Zakarya Kabbara, Sandy Jorens, Peter Hellinckx, Ivan Verhaert
Key points
From the paper's conclusion- The results further demonstrate that VAV system behavior cannot be represented by a single system curve, but instead corresponds to a controller-dependent operating envelope defined by the interaction between demand profiles, network layout, VAV constraints, fan characteristics, and control dynamics.
Abstract
Variable Air Volume (VAV) ventilation systems are widely used in non-residential buildings because they allow airflow to be adjusted to zone-level demands. In practice, however, many systems are still operated with a Constant Static Pressure (CSP) setpoint, which leads to excessive duct pressure, increased VAV damper throttling, and unnecessary fan energy use under partial-load conditions. Static Pressure Reset (SPR) strategies can mitigate this inefficiency, but practical implementations are typically based on heuristic trim-and-respond logic and are influenced by VAV flow-control dynamics, actuator response, fan-map limitations, and minimum terminal pressure requirements. This paper presents a component-level simulation framework to assess VAV fan-control strategies under consistent physical conditions. Three strategies are compared: CSP, an ideal model-based SPR lower bound, and a practical dynamic SPR controller. The results show that the ideal SPR reduces fan energy by 56.3% relative to CSP, while the practical controller achieves a 43.9% reduction, representing 78.1% of the theoretical saving potential. The results further demonstrate that VAV system behavior cannot be represented by a single system curve, but instead corresponds to a controller-dependent operating envelope defined by the interaction between demand profiles, network layout, VAV constraints, fan characteristics, and control dynamics.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- VENTILA2: A Fuzzy Logic-Based Simulation and Decision-Support Framework for Pressure-Controlled Ventilation-A Proof of Concept.Healthcare (Basel, Switzerland) · 2026
- Retrofitting centralized air compressor stations with end-use-aware predictive set-pressure control using a physics-constrained pressure-drop modelarXiv · 2026
- Experimental Comparison of Control Strategies for Heat Recovery from Compressors Under Variable Operating ConditionsEnergies · 2026
- Experimental Comparison of Guideline 36 and Legacy Controller Sequences of Operation using Commercial-off-the-shelf Control Software.Science and technology for the built environment · 2026
- Passive Design Involving Multi-Performance Optimization and Cascading Optimization of Active Airflow Mode for the Sentry Box BuildingsBuildings · 2026
- Impact of ventilation strategy during the transition phase of ARDS: Synchronized vs. non-synchronized pressure-regulated vs. volume-controlled mode - A randomized crossover study.Annals of intensive care · 2026