arXivPreprintOpen accesseess.SY

Retrofitting centralized air compressor stations with end-use-aware predictive set-pressure control using a physics-constrained pressure-drop model

Taito Watanabe, Yohei Kono, Akira Iyozumi, Takashi Nakajima

Key points

From the paper's conclusion
  • A lightweight hierarchical nonlinear model predictive control (NMPC) scheme, retrofitted to the sequencing controller of a centralized compressor station typical of small and medium-sized plants, lowers the set pressure as far as the end-use requirement allows.

Abstract

Compressed air systems usually run at a constant set pressure well above the end-use requirement; the excess margin is wasted energy. A lightweight hierarchical nonlinear model predictive control (NMPC) scheme, retrofitted to the sequencing controller of a centralized compressor station typical of small and medium-sized plants, lowers the set pressure as far as the end-use requirement allows. It uses only two pressure gauges (receiver and one critical end-use point) and compressor data, without flow meters or piping surveys. The end-use pressure is predicted by a low-order pressure-drop model identified by least squares under stability, damping and steady-state equilibrium constraints, which serve use rather than accuracy: they let the measured pressure drop be held over the horizon with unit gain. Validated in three stages (plant data, a pipe-network simulator checked against measurements, and the actual controller, at most 1.41 s per update), the NMPC meets the required pressure under real demand and reduces the estimated annual energy consumption by 2.8 % relative to the current constant operation (9.3 % relative to 0.70 MPa). A PID cascade with the same gauge saves about as much only when tuned by a standard rule at its recommended setting from a constant-load step test, difficult in an operating plant; the NMPC needs no such test and keeps its performance with its initial model and default weights after plant expansion and network split. The margin becomes a design parameter instead of a fixed excess, and the controller's signals show where the supply system lacks headroom.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Retrofitting centralized air compressor stations with end-use-aware predictive set-pressure control using a physics-constrained pressure-drop model — Science Skim