Key points
From the paper's conclusion- Addressing the challenge of evaluating electricity meter measurement errors caused by nonlinear high-power dynamic loads in smart grids, as well as the issues of long cycle periods and high time consumption associated with traditional m-sequence test signals, this paper proposes an indirect error measurement method based on dynamic test signal modeling using random measurements.
Abstract
Addressing the challenge of evaluating electricity meter measurement errors caused by nonlinear high-power dynamic loads in smart grids, as well as the issues of long cycle periods and high time consumption associated with traditional m-sequence test signals, this paper proposes an indirect error measurement method based on dynamic test signal modeling using random measurements. Firstly, compressive sensing theory is introduced to construct a structured Orthogonal Pseudo-Random Measurement (OPRM) matrix, generating a dynamic test signal that balances randomness and compactness. This achieves a significant dimensionality reduction of the test sequence while accurately preserving the stochastic fluctuation characteristics of actual dynamic loads. Secondly, a "Run-length Likelihood Function" for dynamic electrical energy is innovatively defined. Leveraging a high-precision synchronous gating control mechanism to eliminate time-domain random truncation effects, a rigorous mapping model is established for tracing dynamic reference energy back to the steady-state reference value. Experimental verification demonstrates that the OPRM model's capability to reflect dynamic errors is highly consistent with that of the traditional m-sequence. However, the single-test duration is drastically reduced from 197 to 49 min, achieving a 75% reduction in time cost. Concurrently, the system's test repeatability is as low as 0.0003%, and the expanded uncertainty is strictly constrained at 0.1442% (inclusion factor k = 2), pushing the comprehensive measurement accuracy of dynamic metering to a new high of better than 0.15%. This work provides core technical support for the agile and high-precision calibration of massive smart electricity meters.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Online Evaluation of Measurement Uncertainty in Sensor Networks: A Case Study on Voltage TransformersIEEE Transactions on Industrial Informatics · 2026
- Measurement error detection of electric vehicle charging pile operation under multi-segment charging data fusionJournal of Physics: Conference Series · 2026
- Beyond Complete Observability: Reference Model, Protocol Checks and AI Methods for Smart Meter Defect DetectionJournal of Sensor and Actuator Networks · 2026
- Dynamic Spatiotemporal Measurement Uncertainty-Aware Detection for Robust Power System State Estimation Against Stealthy FDIAIEEE Internet of Things Journal · 2026
- Anomaly Detection and Data Repair for Smart Meter Data in Smart Cities: A Comprehensive Review and Future Perspectives.Sensors (Basel, Switzerland) · 2026
- Hierarchical Regime-Conditioned Ornstein–Uhlenbeck Monitoring for Thermal Control in Memory Reliability Test EquipmentMathematics · 2026