Shared-Source Air–Liquid Hybrid Thermal Management and Pareto-Optimized Supervisory Control for Peak-Shaving Battery Energy Storage Systems
Zhiyuan Jiang, Xin Wang, Wenpeng Wang, Hui Wang, Zhiguo Qu, Qiong Wang
Key points
From the paper's conclusion- The results demonstrate that energy savings arise from hierarchical matching of cooling intensity to dynamic thermal demand under a shared cooling source.
Abstract
Battery thermal loads in peak-shaving energy storage systems vary rapidly with power, creating a trade-off between thermal safety and auxiliary energy consumption. This study proposes an air−liquid hybrid thermal management architecture with a shared variable-capacity vapor-compression chiller and develops a pareto-optimized hybrid supervisory control (POHSC) for system-level energy reduction. The chiller supplies both an air coil and liquid cold plates, enabling air-side, liquid-side, or simultaneous cooling without duplicating refrigeration hardware. A five-zone lumped thermal model, identified from three-dimensional conjugate heat-transfer simulations, retains the principal spatial temperature distribution while enabling efficient day-scale control analysis. Offline Pareto optimization determines switching boundaries, and the online controller assigns air cooling to low-to-moderate thermal loads while reserving liquid cooling for short high-load periods. For a representative high-cooling-load day in Xi’an, POHSC limits the maximum zone-average temperature and maximum interzone temperature difference to 30.023 °C and 3.641 K, respectively. Daily auxiliary energy consumption is 18.014 kWh, 20.87% lower than pure liquid cooling. Although the liquid branch operates for only 1.38 h, it removes 61.9% of cumulative heat. The results demonstrate that energy savings arise from hierarchical matching of cooling intensity to dynamic thermal demand under a shared cooling source.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Sustainable Reduced-Order Thermal Modeling for Energy-Efficient Real-Time Control of Grid-Scale Energy Storage SystemsSustainability · 2025
- Modeling Liquid-Cooled Data Centers in EnergyPlusarXiv · 2026
- Thermoelectric-based battery thermal management with cooling and energy recoveryThe Innovation Energy · 2026
- Thermal characteristic analysis and optimization research of new energy vehicle battery thermal management system based on numerical simulationJournal of Engineering and Applied Science · 2026
- Hybrid thermoelectric and air cooling of a 104-cell lithium-ion battery pack coupled with thermal modelling of cooling performance, power cost and safe operating limitsEngineering Research Express · 2026
- Electricity-computility integration of data centers and pumped storage driven by cold energy storage in ChinaEnergy Reports · 2025