arXivPreprintOpen accesseess.SY

Grey-Box Experimental Identification of Reduced-Order Models for Grid-Forming Converters

Marcelo Cardenas, Stephan Kenzelmann, Matteo Saviozzi, Federico Silvestro, Fabrizio Sossan

Key points

From the paper's conclusion
  • This paper proposes a grey-box system identification for identifying and validating reduced-order models (ROMs) of grid-forming (GFM) converters.

Abstract

This paper proposes a grey-box system identification for identifying and validating reduced-order models (ROMs) of grid-forming (GFM) converters. Three reduced-order modeling techniques are compared within a common identification procedure: singular perturbation with frequency cutoff and participation factors (SP-PF), singular perturbation with energy residuals (SP-Energy), and balanced truncation (BT). Testing is on experimental data with real-life components. Results show that BT achieves the highest time-domain fit, followed by SP-Energy and SP-PF; SP-Energy better preserves key properties of the identified full-order model; BT places the dominant mode closest to the stability boundary and exhibits the highest sensitivity to parameter variations; SP-Energy outperforms SP-PF in both fit quality and consistency of modal preservation. Findings suggest that the model with the best time-domain fit does not always provide the most reliable representation of the modal properties for small-signal stability, with SP-Energy offering the best compromise between accuracy, physical interpretability, and modal preservation for the considered case study.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.