EMT-Validated Branch-and-Bound Determination of Robust Small-Signal Stability Regions for Multi-Converter Power Systems Under Joint Operating, Control, Model-Error and Topological Uncertainty
Fan Li, Jishuo Qin, Binqi Ma, Jian Meng, Hanqing Liang, Taikun Tao
Key points
From the paper's conclusion- An average-value electromagnetic-transient model reproduces the candidate device’s positive-rotation admittance with deviations of approximately 0.2% in magnitude and 0.2° in phase at eight frequencies, as well as the strongly unstable system growth rate to about 2%; switching simulations corroborate selected qualitative outcomes.
Abstract
Assessing additional converter capacity requires stability analysis under operating, control, device-model and network-topology uncertainty. This paper integrates structured singular value analysis with branch and bound to assess regions in engineering coordinates, including capacity, short-circuit ratio, synchronisation bandwidth and reactive support. Each box undergoes equilibrium screening and structured uncertainty analysis; candidate instability is confirmed by reconstructing a physical scenario and applying a winding-number test. On a nine-bus, six-device system, the computation assigns 8.34% of the domain to verified robust boxes, 38.80% to undecided boxes, 18.49% to boxes containing confirmed instability witnesses and 34.37% to boxes rejected by equilibrium screening. Verification on a 44-point frequency grid reduces the initial robust share from 19.01% to 8.34%. Under a fixed stressed scenario, the critical capacity is bracketed between 477.148 and 477.178 MW. An average-value electromagnetic-transient model reproduces the candidate device’s positive-rotation admittance with deviations of approximately 0.2% in magnitude and 0.2° in phase at eight frequencies, as well as the strongly unstable system growth rate to about 2%; switching simulations corroborate selected qualitative outcomes. The contribution is the integrated planning workflow. Its reported coverage depends on refinement and identification quality and remains conditional on sampled equilibrium and residual assessments and finite-frequency evaluation.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Minimal Behavioral Contracts for Compositional Stability of Multi-Vendor Converter-Dominated Power SystemsEnergies · 2026
- Modular Model Order Reduction for Inverter-Based Power Systems with Stability and Accuracy GuaranteesarXiv · 2026
- Layered Multi-Resource Restoration Control Under Nonsmooth Stability-Margin Constraints for Converter-Dominated Power GridsElectronics · 2026
- Measurement-Driven Koopman Dynamic Equivalencing with Modal Preservation for Small-Signal Stability Assessment of Power SystemsSensors · 2026
- Dynamic System Strength as Structured Stress Radii with Complete Contribution Allocation for Converter-Dominated Multiport GridsElectronics · 2026