arXivPreprintOpen accesseess.SY

Travelling-Wave-Based Protection of DC Hubs in Bipolar HVDC Grids

Rahul Rane, Victor Daniel Reyes Dreke, Wilhelm Winter, Aleksandra Leki\'c

Key points

From the paper's conclusion
  • The results demonstrate the feasibility of real-time implementation and characterize the effects of fault location and travelling-wave propagation on transient energy and protection response time.

Abstract

This paper presents a stationary wavelet transform (SWT)-based method for DC fault detection and classification in a three-terminal bipolar modular multilevel converter (MMC)-based HVDC system with a dedicated metallic return (DMR). The system incorporates DC switching stations (DCSSs) with interconnected DC circuit breakers (DCCBs). The method uses line-mode voltage wavelet detail energy for fault detection and wavelet detail energy derived from pole voltages and DMR current for fault classification, distinguishing pole-to-pole, pole-to-ground, and pole-to-DMR faults. Its performance is evaluated using a real-time hardware-in-the-loop (HIL) platform integrating an real-time digital simulator (RTDS) with embedded processing hardware. Busbar and cable faults with varying fault types, resistances, and locations are investigated. The results demonstrate the feasibility of real-time implementation and characterize the effects of fault location and travelling-wave propagation on transient energy and protection response time. The effectiveness of pole-voltage and DMR-current detail energy features in distinguishing fault types is also evaluated.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers