AI Surge Accelerates the Transition to Liquid Cooling: Rethinking Energy and Water Use in Data Center Cooling
Yingbo Zhang, Eric Masanet, Shengwei Wang
Key points
From the paper's conclusion- We identify global free-cooling rack inlet temperature thresholds of 33 $^\circ$C for evaporative systems and 49 $^\circ$C for dry systems, demonstrating the practicality of 100% free cooling in many locations.
Abstract
The power density of AI workloads is rapidly driving shifts to liquid cooling. This study rethinks and assesses the global impact on energy and water demand of this cooling transformation. Results suggest that liquid cooling can reduce cooling energy use by 25-56% relative to air cooling, offering substantial energy savings for GW-scale AI data centers. Best-practice PUE values could be as low as 1.07-1.08 for today's systems and 1.03-1.04 for emerging designs, and WUE values range from 0.38 to 2.63 L/kWh, depending on temperature conditions. We identify global free-cooling rack inlet temperature thresholds of 33 $^\circ$C for evaporative systems and 49 $^\circ$C for dry systems, demonstrating the practicality of 100% free cooling in many locations. The model finds that minimum PUEs do not necessarily coincide with minimum total energy use, because warmer coolant raises server power. Results quantify the large sustainability potential of liquid cooling and provide actionable targets for data center design and policies.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Modeling Liquid-Cooled Data Centers in EnergyPlusarXiv · 2026
- Operational analysis of the cooling system in a direct liquid-cooled data center: a measurement and simulation study on the impact of supply water temperatureApplied Energy · 2025
- Integrated Thermal and Energy Optimization of a Solar-Powered 500 MW AI Data Center in Central North TexasApplied Sciences · 2026
- Energy and carbon savings in data centres through liquid-to-chip cooling with differential temperature controlAdvances in Applied Energy · 2026
- Performance evaluation of two-phase direct-to-chip liquid cooling combined with air cooling for data centersCase Studies in Thermal Engineering · 2026
- Holistic energy analysis method for thermal management architectures of data centersInternational Journal of Heat and Mass Transfer · 2026