arXivPreprintOpen accesseess.SY

Beyond Scalar Inertia: Frequency-Response-Based Assessment of Finite-Duration Inertial Support in Grid-Forming Converters

Ziqi Zhou, Mahdieh S. Sadabadi, Sante Pugliese, Xiaoqiang Li, Xiaojie Wu, Marco Liserre

Key points

From the paper's conclusion
  • Conventional scalar inertia characterizes only the low-frequency terminal behavior of grid-forming converters (GFMs) and cannot fully predict inertial energy delivery during short-duration frequency disturbances.

Abstract

Conventional scalar inertia characterizes only the low-frequency terminal behavior of grid-forming converters (GFMs) and cannot fully predict inertial energy delivery during short-duration frequency disturbances. This letter proposes a frequency-response-based method to assess finite-duration inertial support using complex terminal power--frequency responses, such as those provided by Network Frequency Perturbation (NFP) plots. For GFMs with nonzero steady-state droop, a duration-dependent energy-equivalent inertia is defined after subtracting the ideal static-droop contribution. An exact spectral relationship is established, expressing this metric as a duration-weighted integral of frequency-dependent inertia, without requiring knowledge of the internal controller structure and parameters. The duration dependence of the metric is further shown to encode observable oscillation frequencies and damping ratios. A coefficient-decoupling GFM control with identical scalar inertia and droop across different settings is used for verification.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Beyond Scalar Inertia: Frequency-Response-Based Assessment of Finite-Duration Inertial Support in Grid-Forming Converters — Science Skim