Frequency Measurement Practices for Inertia Assessment in Inverter Based Resources Dominated Power Systems
Christos M. Nikolakakos, Hassan Haes Alhelou, Nikos Hatziargyriou
Key points
From the paper's conclusion- Fast frequency response inflates the estimate most: at 500 ms a grid-following system with 20 % less synchronous inertia reports the same value as the all-synchronous system, the grid-forming system a higher one.
Abstract
Transmission system operators and protective relays compute the rate of change of frequency (RoCoF) from frequency averaged over tens to hundreds of milliseconds, as standards and grid codes specify. Any response delivered inside that window lowers the measured RoCoF, so the inferred inertia depends on the window and the responses in service. This paper defines the windowed inertia estimate and derives an exact identity the system inertia divided by one minus the fraction of the disturbance energy delivered inside the window and a closed-form prediction that applies the same estimator to the trajectory of a linear response model. Eleven IEEE 9-bus RMS runs synchronous, grid-following and grid-forming configurations, disturbance sizes and parameter sweeps are reproduced by that model, and the identity closes on the measured response powers. Fast frequency response inflates the estimate most: at 500 ms a grid-following system with 20 % less synchronous inertia reports the same value as the all-synchronous system, the grid-forming system a higher one. On a reduced Greek transmission system the 500ms estimate exceeds the inertia by 17-26%, and a scenario with 10% less synchronous inertia reports more than the all-synchronous scenario's inertia. Operators can thus compute what their measurement reports.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Inertia estimation for power grids: A review of methods, challenges, and future prospectsApplied Energy · 2026
- Beyond Scalar Inertia: Frequency-Response-Based Assessment of Finite-Duration Inertial Support in Grid-Forming ConvertersarXiv · 2026
- Measurement-Based Assessment of Decadal Inertia and Primary Frequency Response Trends in the US Eastern InterconnectionarXiv · 2026
- Evaluating the minimum inertia of power systems with consideration for wind power in frequency regulationInternational Journal of Electrical Power & Energy Systems · 2026
- Modeling and Mitigation of Spatial–Temporal Frequency Patterns in IBR-Dominated Power SystemsElectronics · 2026
- Hyperscale Data Centers as Wide-Area Damping Actuators for Low-Inertia Power SystemsarXiv · 2026