Grid-forming Control of Offshore Wind through a Diode-Rectifier HVDC System: a 2 GW Case Study
Ishi Nigam, Saif Alsarayreh, Tuanku Badzlin Hashfi, Milo\v{s} Cvetkovi\'c, Joris van Doorn, Aleksandra Leki\'c
Key points
From the paper's conclusion- Extending the system to 2 GW with two 500 MW grid-following units achieves full power transfer in simulation, but with the grid-forming converter loaded beyond its continuous rating and a steady-state offshore frequency deviation of approximately 1.8 Hz.
Abstract
Diode-rectifier-unit (DRU)-based high-voltage direct current (HVDC) transmission considerably reduces the volume and weight of the offshore converter platform for remote wind farms and, hence, its cost, but shifts the task of forming and regulating the offshore AC network to the wind-turbine converters. This paper examines which grid-forming control strategy is the most suitable for DRU power transfer. The DRU commutation relationship shows that the delivered active power depends on the offshore voltage magnitude (but not on the converter voltage angle), so the angle-based active-power loop of virtual synchronous machine control is not closed through the rectifier. A $P-V/Q-{\omega}$ grid-forming architecture, which regulates active power via the voltage magnitude and derives frequency from the reactive power error, is therefore adopted. Electromagnetic transient simulations of a 1GWaggregated grid-forming turbine on a 66 kV collector network with a $\pm$525 kV bipolar DRU link show that the commanded power is delivered over 800 to 1000MW with the offshore voltage held near nominal. The paper also examines how grid-forming operation changes the allocation of control duties within the Type-4 turbine: once the grid-side converter forms the network, DC link regulation must move to the machine-side converter, which limits the achievable bandwidth of the DC-link control. Extending the system to 2 GW with two 500 MW grid-following units achieves full power transfer in simulation, but with the grid-forming converter loaded beyond its continuous rating and a steady-state offshore frequency deviation of approximately 1.8 Hz.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Enhancing stability in renewable energy transmission using multi-terminal HVDC systems with grid-forming controls for offshore and onshore wind integrationScientific Reports · 2025
- Sub-Synchronous and Super-Synchronous Oscillation Propagation in Offshore Wind Farms with Hybrid DRU MMC HVDC TransmissionProcesses · 2026
- Frequency Feature Transfer and Coordinated Control Algorithm for Offshore Wind MMC-HVDC Systems Based on DC Voltage FluctuationElectronics · 2026
- Fast Active Power Reduction Based Fault Ride-Through Control Strategy for VSC-HVDC Integrating Offshore Wind Farm Under Onshore FaultIEEE Transactions on Sustainable Energy · 2026
- Dc-link voltage regulation in all-DC offshore wind farmsElectrical Engineering · 2026
- Research on hierarchical coordinated variable-gain frequency regulation strategy for wind farm MMC-LCC grid-connected systemInternational Journal of Electrical Power & Energy Systems · 2026