The one-step surface-air lag in the EnergyPlus zone heat balance: order of accuracy, correction and consequences

Wooyoung Jung

Key points

From the paper's conclusion
  • This study measured that order for the zone heat balance of EnergyPlus 26.2 against exact or converged references and tested a correction on 45 U.S.

Abstract

The order of accuracy sets how fast numerical error falls as the timestep shortens. This study measured that order for the zone heat balance of EnergyPlus 26.2 against exact or converged references and tested a correction on 45 U.S. Department of Energy prototype cases. All three zone air formulas, the third-order default included, give first order or lower, because the surfaces use the previous timestep's air temperature. Solving surfaces, air and HVAC to agreement within each timestep raises the default to about second order, and in a room with an exact solution two extra passes cut the error eightfold at 1.65 times the runtime. In the prototype cases, the correction changed annual site energy by at most 0.45% but an outpatient clinic's heating by 5.1%. Window-upgrade savings changed by 10% or more in 13 of the 34 applicable cases, about as often as under a change of timestep.