The one-step surface-air lag in the EnergyPlus zone heat balance: order of accuracy, correction and consequences
Wooyoung Jung
Key points
From the paper's conclusion- This study measured that order for the zone heat balance of EnergyPlus 26.2 against exact or converged references and tested a correction on 45 U.S.
Abstract
The order of accuracy sets how fast numerical error falls as the timestep shortens. This study measured that order for the zone heat balance of EnergyPlus 26.2 against exact or converged references and tested a correction on 45 U.S. Department of Energy prototype cases. All three zone air formulas, the third-order default included, give first order or lower, because the surfaces use the previous timestep's air temperature. Solving surfaces, air and HVAC to agreement within each timestep raises the default to about second order, and in a room with an exact solution two extra passes cut the error eightfold at 1.65 times the runtime. In the prototype cases, the correction changed annual site energy by at most 0.45% but an outpatient clinic's heating by 5.1%. Window-upgrade savings changed by 10% or more in 13 of the 34 applicable cases, about as often as under a change of timestep.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Anchor-Corrected Grey-Box Soft-Sensing Control for Multi-Zone Heating Systems Under Sparse Indoor-Temperature Sensing: Time-Scale Alignment and Common-Mode Residual CompensationEnergies · 2026
- Heating Buildings Only When Needed: A Data-Driven Based Framework for Comfort-Aware HVAC SchedulingBuildings · 2026
- Einfluss der Gebäudemodellkomplexität auf die Simulation gekoppelter EnergiesystemeBauphysik · 2026
- A reduced-order model for predicting transient performance of air-source heat pumpsApplied Energy · 2026
- When Is a Room Error an HVAC Error? A Task-Aware Evaluation Framework for Floor-Plan Room Reconstruction Using Thermal-Zone Proxies and Design LoadsBuildings · 2026
- Adjacent Heat Transfer Effects Can Bias Savings Estimates When Controlling Only Part of a Multi-Zone BuildingarXiv · 2026