Attack-Resiliency Analytics for Wide-Area Control Systems in Smart Grids
Mohammad Zakaria Haider, Prabin Mali, Nur Imtiazul Haque, Muhammad Nadeem, Sumit Paudyal, Mohammad Ashiqur Rahman
Key points
From the paper's conclusion- On the IEEE 39 and 118 bus systems, with reference dynamics validated on an OPAL-RT hardware-in-the-loop testbed, the optimal attack with wide-area access attains 3.3 and 8.1 times the benign objective and reaches a 0.5Hz frequency excursion more than twice as fast as an attack confined to automatic generation control.
Abstract
Wide-area monitoring, protection, and control (WAMPAC) systems damp inter-area oscillations in large interconnected grids, but their reliance on synchronized PMU measurements carried over wide-area networks exposes them to false data injection (FDI) attacks. This paper presents an attack-resiliency analytics framework that formally models the coupled dynamics of the wide-area damping loop, automatic generation control, and the governor and excitation systems, and formulates the optimal stealthy FDI attack as a mixed-integer linear program (MILP). The anomaly detection model (ADM) enters as a replaceable constraint set: either a static bad-data detection (BDD) rule or a boundary learned from benign operation calibrated to a common false-positive rate. On the IEEE 39 and 118 bus systems, with reference dynamics validated on an OPAL-RT hardware-in-the-loop testbed, the optimal attack with wide-area access attains 3.3 and 8.1 times the benign objective and reaches a 0.5Hz frequency excursion more than twice as fast as an attack confined to automatic generation control. Learned boundaries reduce the attack objective by 15.5 55.0% and prevent over-frequency relay trips in all configurations, with feasible stealthy attacks remaining in every case, and residual risk tracks the width of the learned boundary rather than the detector family.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Dynamic Spatiotemporal Measurement Uncertainty-Aware Detection for Robust Power System State Estimation Against Stealthy FDIAIEEE Internet of Things Journal · 2026
- Stealthy, High-Impact False Data Injection Attacks in Smart Grid Using Physics-Constrained GANarXiv · 2026
- An Adaptive Reconstruction and Branch-Interaction Network for False Data Injection Attack Detection in Smart GridsAutomation · 2026
- Securing Wide-area Damping Controller Against Cyber Attacks Using Semi-supervised Generative Adversarial Network and Support Vector Machine-based Synthetic Minority Oversampling TechniqueJournal of Modern Power Systems and Clean Energy · 2026
- Detection of Measurement Replay Attacks in Power Systems Based on Adaptive Dual-Context FusionFuture Internet · 2026
- Interpretable Cyber-Physical Attack Detection in Smart Grids: A Leakage-Controlled Multi-Testbed Evaluation of Fusion, Robustness, and Observability LimitsarXiv · 2026