Detection of Measurement Replay Attacks in Power Systems Based on Adaptive Dual-Context Fusion
Zeyi Hu, Rixuan Qiu, Hong Rao, Sitong Jing
Key points
From the paper's conclusion- We further propose Adaptive Dual-Context Fusion (ADCF), which explicitly models two complementary sources of attack evidence: local temporal context reflecting dynamic evolution of the current system state and window-level association context capturing shifts in the temporal association structure within the current observation window.
Abstract
Measurement replay attacks in power systems tamper with current observations by replacing them with historically legitimate measurements, which may conceal physical anomalies while preserving numerical plausibility and short-term continuity. Existing detection methods based on residual analysis, reconstruction errors, or generic temporal representations may struggle with replay patterns that remain locally smooth but become inconsistent with the current operating trajectory. To address this challenge, we construct an IEEE 39-bus continuous-operation dataset designed to reduce the direct coupling between physical disturbances and attack labels, including paired event-only and event-background replay attacks, normal-background replay attacks, and hard negative scenarios. We further propose Adaptive Dual-Context Fusion (ADCF), which explicitly models two complementary sources of attack evidence: local temporal context reflecting dynamic evolution of the current system state and window-level association context capturing shifts in the temporal association structure within the current observation window. A normalized gated fusion mechanism is introduced to adaptively integrate these two types of evidence according to sample-specific characteristics. Across the 18 simulated event-background replay scenarios, the constructed attacks mask an average of 87.84% of the time points at which the target line is physically overloaded. Under full point-wise test coverage, ADCF achieves a Macro-F1 of 96.61%, an attack-class F1-score of 94.39%, and a PR-AUC of 97.56%, with 93.79% attack recall when the false positive rate (FPR) is constrained to no more than 1%. Ablation studies further show that the two contextual branches provide complementary discriminative information, while sample-wise gated fusion shifts the fixed-threshold trade-off toward higher attack recall.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Dynamic Spatiotemporal Measurement Uncertainty-Aware Detection for Robust Power System State Estimation Against Stealthy FDIAIEEE Internet of Things Journal · 2026
- Attack-Resiliency Analytics for Wide-Area Control Systems in Smart GridsarXiv · 2026
- An Adaptive Reconstruction and Branch-Interaction Network for False Data Injection Attack Detection in Smart GridsAutomation · 2026
- Interpretable Cyber-Physical Attack Detection in Smart Grids: A Leakage-Controlled Multi-Testbed Evaluation of Fusion, Robustness, and Observability LimitsarXiv · 2026
- HKD-ACPA: Heterogeneous Knowledge Distillation Adversarial Cyber-Physical Attacks in Power GridsarXiv · 2026
- Topology-Transferable Detection of Deep-Learning False Data Injection Attacks Through Residual-Energy SeparationarXiv · 2026