Identification of $dq$-Asymmetric Impedances as Complex Transfer Functions Using a Single Arbitrary Excitation
Mohamed Abdalmoaty, Zheran Zeng, Dongsheng Yang, Florian Dörfler
Key points
From the paper's conclusion- Both complex transfer functions and all four real transfer functions of the $dq$ impedance are recovered over a wide band from a single one-second record of a random excitation, at 1 Hz resolution.
Abstract
Cross-coupling between the $dq$ coordinates makes the identification of asymmetric grid impedances a challenging problem, particularly near the fundamental frequency where the asymmetric coupling is strongest. Existing schemes usually handle it either by perturbing the two coordinates sequentially, which lengthens the measurement, or by using a time-domain method with a global parametric model whose order must be tuned. This paper develops a single-shot active non-parametric frequency-domain method that avoids both. The equivalent impedance is parameterized by a pair of single-input single-output complex transfer functions. Each spectral line is fitted with a local rational model; the leakage and transient contributions are estimated, so that neither periodic steady-state excitation nor repeated excitation cycles are required. We give the exact finite-time discrete Fourier transform relation for the conjugate-coupled complex-signal model, and analyse the distortion that a stationary-frame filter placed ahead of the Park transform imposes on the identified pair. The method is validated on a controller hardware-in-the-loop platform against an analytically derived small-signal model, for a symmetric grid and for the same grid with an added grid-following converter that renders it asymmetric. Both complex transfer functions and all four real transfer functions of the $dq$ impedance are recovered over a wide band from a single one-second record of a random excitation, at 1 Hz resolution.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Frequency-Domain Injection-Based Equivalent Impedance Identification for Distribution Networks with High-Penetration Distributed PVElectronics · 2026
- On PMU Adequacy for Wideband Dynamics Tracking Beyond Attenuation AssumptionsarXiv · 2026
- Two Perspectives, One Impedance: Unified dq- and Sequence-Domain Impedance Modeling and Weak-Grid Stability Analysis of Grid-Connected LCL Inverters with Complete Industrial Control LoopsEnergies · 2026
- Enhancing Transient Stability of VSG-Controlled Converters Under Grid Frequency DisturbancesarXiv · 2026
- Active damping and harmonic suppression strategy of LCL Grid-tied inverters based on single inverter-side inductor current feedback considering sampling delayJournal of Physics: Conference Series · 2026
- Multipath Architecture for Ground Fault Detection in DC-Links of High-Voltage AC Drives Using Neutral-Point VoltageJournal of Marine Science and Engineering · 2026