GIS-Informed Thermal Constraints for the Adaptive Protection of Distribution Transformers
Khandoker Islam, Ahmed Abu-Siada, Krzysztof Stegmann, Blair Ward
Key points
From the paper's conclusion- The proposed framework prioritizes thermal permissibility assessment before selecting the appropriate protection setting groups, providing an additional layer of protection that complements conventional transformer fuses.
Abstract
Distribution-network reconfiguration alters fault levels, while elevated ambient temperatures reduce transformer thermal-loading margins. This study proposes a geographic information system (GIS)-informed, thermal-aware network state engine that integrates environmental exposure assessment, standards-based transformer thermal evaluation, electrical transient analyzer program (ETAP) simulations, and pre-validated adaptive protection settings. The Kununurra GIS assessment covers 394 transformer-related asset locations across two seasonal periods: the wet season (November 2024–April 2025) and the dry season (May–October 2025). The assessment integrates Landsat-derived land surface temperature (LST), ERA5-Land ambient air temperature, Bureau of Meteorology observations, and spatial asset buffers ranging from 50 to 250 m. At the 100 m buffer, the mean site-level LST was 41.34 °C during the wet season and 38.34 °C during the dry season, while the corresponding mean temporal 95th-percentile (P95) LST values were 49.28 °C and 50.51 °C, respectively. Seasonal correlations between the normalized difference vegetation index (NDVI) and LST were negative. Notably, only 8 of the 40 hottest sites identified at the 100 m buffer remained among the top 40 across both seasons, highlighting substantial seasonal variability in thermal exposure. These findings highlight the importance of periodically updated spatial exposure assessments, while recognizing that LST should not be interpreted as transformer cooling-air temperature. For a representative 315 kVA transformer, ETAP-based ambient temperature derating reduced the available capacity from 315 kVA at 30 °C to 257.6 kVA at 50 °C, demonstrating the impact of elevated ambient temperatures on transformer loading capability. Feeder reconfiguration increased the three-phase fault current from 3.134 to 8.485 kA. In a supplementary SEL-121F relay sensitivity assessment, the prospective backup operating time decreased from 1.677 to 0.735 s. The proposed framework prioritizes thermal permissibility assessment before selecting the appropriate protection setting groups, providing an additional layer of protection that complements conventional transformer fuses.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Benefits of Dynamic Thermal Rating for Distribution Transformers Under Accelerated Load GrowtharXiv · 2026
- Prediction of Transformer Load-Rate and Analysis of Meteorological Feature Contributions for Sustainable Operation of Regional Substations: An Explainable Machine Learning ApproachSustainability · 2026
- Harmonic Distortion and Distribution Transformer Thermal Risk in Low-Voltage Networks: Feeder Impedance Sensitivity for Sustainable Renewable Energy IntegrationSustainability · 2026
- Heatwave-induced capacity bottlenecks in European electricity gridsNature Energy · 2026
- Spatiotemporal dynamic lightning damage risk assessment for high-altitude distribution lines considering seasonal surface evolution and time-varying lightning withstand capabilityFrontiers in Energy Research · 2026
- Dynamic Line Ratings Counteract Transmission Investment Needs Driven by Climate ChangearXiv · 2026