Mechanical Fault Diagnosis of High-Voltage Circuit Breakers Based on Multi-Sensor Gramian Angular Field and Deep Residual Network.
Xining Li, Hanyan Xiao, Ke Zhao, Lei Sun, Tianxin Zhuang, Haoyan Zhang, Hongwei Mei
State Grid Jiangsu Electric Power Research Institute, Nanjing 211103, China. · Shenzhen International Graduate School, Tsinghua University, Shenzhen 518055, China.
Key points
From the paper's conclusion- The results should be interpreted as proof-of-concept evidence on controlled simulated faults; validation on temporally separated field data, other breaker types and voltage levels, and naturally imbalanced fault distributions remains necessary before broad condition-based-maintenance deployment.
Abstract
The mechanical reliability of high-voltage circuit breakers (HVCBs) is crucial for power-grid stability, yet traditional diagnostic methods rely heavily on manually extracted scalar features that can discard transient information. This paper presents a mechanism-aware diagnostic pipeline that combines synchronized coil-current, contact-travel, and spring-pressure measurements; Variational Mode Decomposition (VMD); kinematics-driven Region of Interest (ROI) alignment; Gramian Angular Field (GAF) encoding; RGB channel stacking; and ResNet-18 classification. On a controlled 220 kV experimental platform covering five operating conditions and 1500 operating-cycle samples, the framework achieved an average accuracy of 96.18% (macro-precision 96.10%, recall 96.01%, and F1-score 96.05%) under five repeated stratified 2:1 holdout evaluations. Single-channel controls obtained 88.47% for current, 90.24% for travel, and 85.13% for pressure; removal of VMD and ROI reduced accuracy to 94.72% and 93.46%, respectively. The results should be interpreted as proof-of-concept evidence on controlled simulated faults; validation on temporally separated field data, other breaker types and voltage levels, and naturally imbalanced fault distributions remains necessary before broad condition-based-maintenance deployment.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Vibration and Coil-Current Fusion for Mechanical Fault Diagnosis of High-Voltage Circuit Breaker Operating MechanismsEnergies · 2026
- Multi-Parameter Fusion-Based Operational State Assessment for HV GIS Disconnector MechanismsEnergies · 2026
- Mechanical fault detection of vacuum circuit breakers in primary lines of power systems based on bidirectional long short-term memory networkJournal of Physics: Conference Series · 2026
- IGAF-MFBLS: A Multimodal Fusion Algorithm for Power Transformer Mechanical Fault DiagnosisEntropy · 2026
- Investigation on Electromagnetic–Thermal–Mechanical Multi-Physics Field Characteristics of GIS Disconnector Under Different Contact ConditionsEnergies · 2026
- Explainable Remaining Useful Life Prediction of Air Circuit Breakers via Physics-Informed Electro-Mechanical Feature Fusion.Sensors (Basel, Switzerland) · 2026