Energies

Vibration and Coil-Current Fusion for Mechanical Fault Diagnosis of High-Voltage Circuit Breaker Operating Mechanisms

Yanlei Yuan, Xinyan Feng, Zhihai Lu, Jian Chen, Chao Yan, Yang Li, Fuqiang Ren, Zihan Li,

Key points

From the paper's conclusion
  • This study experimentally evaluates a specific compact workflow using feature-level fusion on a 40.5 kV outdoor vacuum circuit breaker under normal operation, bolt loosening, opening-spring force degradation, and non-latching closure.

Abstract

Vibration and coil-current signals provide complementary information on the mechanical condition of high-voltage circuit breaker operating mechanisms. This study experimentally evaluates a specific compact workflow using feature-level fusion on a 40.5 kV outdoor vacuum circuit breaker under normal operation, bolt loosening, opening-spring force degradation, and non-latching closure. Signal-specific preprocessing uses variational mode decomposition (VMD)-assisted wavelet soft-threshold denoising for vibration and direct wavelet soft-threshold denoising for coil current. Box dimensions of local mean decomposition (LMD) component power spectra and closing-coil current timing and amplitude descriptors are fused, reduced by principal component analysis, and classified using K-nearest neighbors. The fused model correctly identifies 117 of 120 test samples (97.50%), compared with 87.50% for vibration alone, 90.00% for current alone, and 90.83% without dimensionality reduction. These results support the selected representation for the evaluated breaker, four conditions, and reported test partition under controlled no-load operation. Validation on independent breakers and under field conditions is needed before broader application.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers