Key points
From the paper's conclusion- Motivated by cable fire early warning in power cable tunnels, this study uses cable-fire records from a publicly available indoor EN 54 fire-test-room dataset with distributed multi-sensor nodes to evaluate the proposed model under controlled laboratory conditions.
Abstract
Power cable tunnels are typical enclosed cable-routing spaces in which cable overheating, insulation aging, and partial discharge may gradually develop into fire hazards. During the early stage of cable fires, abnormal sensor responses are often weak, localized, and continuously evolving, which increases the difficulty of early warning based on a single sensor or a single temporal feature. Motivated by cable fire early warning in power cable tunnels, this study uses cable-fire records from a publicly available indoor EN 54 fire-test-room dataset with distributed multi-sensor nodes to evaluate the proposed model under controlled laboratory conditions. In monitoring scenarios with fixed sensor nodes, temporal-only modeling methods often struggle to simultaneously characterize short-term variations, temporal evolution, and spatial differences in node responses. To address this limitation, this study proposes a multi-sensor spatiotemporal feature fusion model that integrates a gated recurrent unit (GRU), a Modern Temporal Convolutional Network (ModernTCN), and an enhanced graph convolutional network (GCN+). The proposed model adopts the ModernTCN as the temporal modeling backbone. A GRU module is introduced at the front end to encode local fluctuations and short-term continuous changes between consecutive time steps, while GCN+ is embedded at the intermediate feature stage of the backbone to model spatial correlations and cross-node coordinated responses among fixed sensor nodes. Experimental results show that the proposed model achieves strong classification performance in the cable fire early warning discrimination task, with a test accuracy of 0.9884 and a false negative rate (FNR) reduced to 0.0150. The comparative experimental results indicate that the proposed model achieves better overall performance than typical temporal baseline models. The ablation study further shows that, under the experimental settings of this study, the introduction of GRU and GCN+ leads to overall improvements in the main evaluation metrics, suggesting that both modules provide a certain enhancement to the cable fire early warning discrimination performance of the ModernTCN backbone.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Research on Intelligent Diagnosis of Sensor Faults on Pipe-Rack Offshore Platform Under Typhoon ActionJournal of Marine Science and Engineering · 2026
- Research on cable condition evaluation method based on multi-sensor information fusionAIP Advances · 2026
- Prediction of Cable Thermal Failure in Switchgear Rooms of Nuclear Power Plants Based on Numerical Simulation and Deep LearningFire · 2026
- Spatial-Temporal Graph Convolutional Network for Fault Diagnosis in Weak Electrical SystemsInformatica · 2026
- Foundation Models Meet Power Grid Topology for Cascade PredictionarXiv · 2026
- Generative Reconstruction of Full-Field Sensor States for Safety-Critical Digital TwinsarXiv · 2026